| Plan Review Notes For Permit 03110015 |
| Permit Number |
03110015 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-11-14 00:00:00 | 1) FIRE ALARM NOTES # 17 IS INCORRECT. | | | WHEN ACTIVATED, THE DUCT SMOKE DETECTOR | | | SHALL CAUSE AN ALARM NOT A SUPERVISORY | | | SIGNAL. | | | | | | 2) FIRE ALARM NOTES # 19 IS INCORRECT. | | | FIRE ALARM CIRCUITS SHALL BE CLASS A, | | | STYLE D, OR FULLY ADDRESSABLE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|