| Plan Review Notes For Permit 03110015 |
| Permit Number |
03110015 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-11-05 00:00:00 | PLEASE SEE THAT ONE SET IS BEING KEPT | | | FOR RECORD OF SAID CORRECTIONS. | | 2003-11-04 00:00:00 | ************ UNSAT **************** | | | | | | 1)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125%. 215.3, 230.42 ETC. | | | | | | 2)NOTE: PLEASE HAVE PLANS "SIGNED" | | | BY THE ENGINEER OF RECORD. IN ORDER TO | | | VERIFY AUTHENTICITY OF ENGINEER'S WORK, | | | AND SIGNATURE PER FS 471.025 PLANS AND | | | REVISIONS WILL BE REQ'D TO BE SIGNED | | | WITH A COMPLETE SIGNATURE INSTEAD OF | | | INITIALS. PLEASE ALSO SEE FAC 61G15-23. | | | 002. | | | THE ABOVE MAY BE SUBMITTED TO THE FBPE | | | FOR REVIEW AND INTERPERTAION. | | | BLDG OFFICAL HAS ALSO RULED THAT PLANS | | | MUST BE SIGNED AND NOT A PRINTED | | | INITIALS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|