Plan Review Notes
Plan Review Notes For Permit 03110015
Permit Number 03110015
Review Stop E
Sequence Number 1
Notes
Date Text
2003-11-05 00:00:00PLEASE SEE THAT ONE SET IS BEING KEPT
 FOR RECORD OF SAID CORRECTIONS.
2003-11-04 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215.3, 230.42 ETC.
  
 2)NOTE: PLEASE HAVE PLANS "SIGNED"
 BY THE ENGINEER OF RECORD. IN ORDER TO
 VERIFY AUTHENTICITY OF ENGINEER'S WORK,
 AND SIGNATURE PER FS 471.025 PLANS AND
 REVISIONS WILL BE REQ'D TO BE SIGNED
 WITH A COMPLETE SIGNATURE INSTEAD OF
 INITIALS. PLEASE ALSO SEE FAC 61G15-23.
 002.
 THE ABOVE MAY BE SUBMITTED TO THE FBPE
 FOR REVIEW AND INTERPERTAION.
 BLDG OFFICAL HAS ALSO RULED THAT PLANS
 MUST BE SIGNED AND NOT A PRINTED
 INITIALS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]