| Date |
Text |
| 2003-11-18 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03110011 |
| | ADD: 2951 ELECTRONIC WAY |
| | CONT: ANDERSON-MORE |
| | TEL: (561)753-7400 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ACTION: DENIED |
| | |
| | 1)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 2)FL S. S. 553.71(7) " THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN |
| | CY CLASSIFICATION AS DEINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS |
| | 5,000 SQ FT IN AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. |
| | 105.13.1 THE ENFORCING AGENCY SHALL |
| | REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| | SRUCTURAL INSPECTIONS ON A THRESHOLD |
| | BUILDING PURSUANT TO A STRUCTURAL INSPEC |
| | TION PLAN PREPARED BY THE ENGINEER OF |
| | RECORD. THE STRUCTURAL INSPECTION PLAN |
| | MUST BE SUBMITTED TO THE ENFORCING AGEN- |
| | CY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESH- |
| | OLD BUILDING. THE PURPOSE OF THE SRUCTUR |
| | AL INSPECTION PLAN IS TO PROVIDE SPECIF- |
| | IC INSPECTION PROCEDURES AND SCHEDULES |
| | SO THAT THE BUILDING CAN BE ADEQUATELY |
| | INSPECTED FOR COMPLIANCE WITH THE |
| | PERMITTED DOCUMENTS. |
| | |
| | 3) PLANS, SPECIFICATIONS,REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | SHEETS : |
| | A-1 NOT SEALED |
| | SURVEY S-1 MISSING SIGNATURE/ DATE |
| | SURVEY S-2 MISSING SEAL/SIGN& DATE |
| | |
| | 4) 104.4.5. SPECIAL FOUNDATION PERMIT |
| | WHEN APPLICATION FOR A PERMIT TO ERECT |
| | OR ENLARGE A BUILDING HAS BEEN FILED, & |
| | PENDING ISSURANCE OF SUCH PERMIT, THE |
| | BUILDING OFFICIAL MAY, AT HIS/ HER |
| | DISCRETION, ISSUE A SPECIAL PERMIT FOR |
| | THE FOUNDATION ONLY, UPON WRITTEN RE- |
| | QUEST OF THE OWNER AND CONTRACTOR. THE |
| | HOLDER OF SUCH A SPECIAL PERMIT IS PRO- |
| | CEEDING AT HIS OR HER OWN RISK AND WITH- |
| | OUT ASSURANCE THAT A PERMIT FOR THE |
| | REMAINDER OF THE WORK WILL BE GRANTED |
| | AND THAT CORRECTIONS WILL NOT BE RE- |
| | QUIRED IN ORDER TO MEET THE PROVISIONS |
| | OF THE TECHNICAL CODE. |