Plan Review Notes
Plan Review Notes For Permit 03101990
Permit Number 03101990
Review Stop E
Sequence Number 1
Notes
Date Text
2003-11-04 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR ALL
 NEW SERVICE EQUIPMENT BEING INSTALLED.
 MAIN DISC/ PANEL AND BRKRS ARE ALL TO
 BE RATED FOR THE AVAILABLE FAULT CURRENT
 PER 110.9 NEC.
  
 2)NOTE: PLEASE SHOW LOADING FOR TRACK
 PER 220.12B
  
 3)NOTE: PLEASE SEE THAT VOLTAGE SHOW ON
 PANEL AND RISER IS SHOWN AT 120/208V
 AND ELECTRICAL SPECS SHOW VOLTAGE AT
 120/220? PLEASE CORRELATE.
  
 4)NOTE: PLEASE VERFIY CIRCUITING FOR
 EM/EXT LTS PER 700.12E.
 SHOW ALL CIRCUITING.
  
 5)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215.3/230.42 ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]