| 2004-01-21 00:00:00 | | | | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} 61G15-23.002 FAC REQUIRES AN ADDRESS | | | ON THE TITLE BLOCK. | | | | | | 2} PLEASE NOTE THAT LOAD CALCULATIONS | | | MUST COMPLY WITH 220.31(B) WHEN USING | | | THE OPTIONAL METHOD FOR AN EXISTING | | | RESIDENCE. | | | | | | 3} PLEASE LIST ALL THE REQ'D | | | DEDICATED BATH(S) CIRCUIT(S) ON PANEL | | | SCHEDULE. PER 210.52D, 210.11C3 | | | 20AMP & #12 WIRE,SEE ARTICLE. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] |
|