Plan Review Notes
Plan Review Notes For Permit 03101853
Permit Number 03101853
Review Stop E
Sequence Number 2
Notes
Date Text
2003-12-17 00:00:00 
 FAILED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 SEE NOTES FROM PREVIOUS REVIEW THAT
 WERE NOT ADDRESSED.
  
 1} LOAD CALCULATIONS PER 230.31(B).NOTE
 #2.
  
 2} SMOKE DETECTORS MUST COMPLY WITH 210.
 12,MUST BE ARC FAULT PROTECTED. SEE NOTE
 #4.
  
 3} REFERRENCE TO "SPARK ARRESTOR DOES
 NOT COMPLY WITH 210.12,SEE NOTE #5.
  
 4} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.SEE NOTE #6.
  
 5} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210.11.(C)(3)
 MUST BE 20A AND #12AWG.SEE NOTE #7
  
 6} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210.52E,SEE NOTE #8.
  
 7} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STAIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 NOTE THAT THE KITCHEN IS LABELED AS
 "EXISTING BEDROOM".
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
 PREVIOUS NOTES ARE ATTACHED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718