| 2003-12-17 00:00:00 | |
| | FAILED |
| | ~~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | SEE NOTES FROM PREVIOUS REVIEW THAT |
| | WERE NOT ADDRESSED. |
| | |
| | 1} LOAD CALCULATIONS PER 230.31(B).NOTE |
| | #2. |
| | |
| | 2} SMOKE DETECTORS MUST COMPLY WITH 210. |
| | 12,MUST BE ARC FAULT PROTECTED. SEE NOTE |
| | #4. |
| | |
| | 3} REFERRENCE TO "SPARK ARRESTOR DOES |
| | NOT COMPLY WITH 210.12,SEE NOTE #5. |
| | |
| | 4} PLEASE NOTE KITCHEN COUNTER- |
| | -SPACE RECEPT SPACING SHALL MEET ART; |
| | 210-52C 1,2,3,4,AND 5.SEE NOTE #6. |
| | |
| | 5} PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S). PER 210.11.(C)(3) |
| | MUST BE 20A AND #12AWG.SEE NOTE #7 |
| | |
| | 6} PLEASE NOTE FRONT AND REAR |
| | RECEPTS REQ`D PER 210.52E,SEE NOTE #8. |
| | |
| | 7} SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | IN THE VICINITY OF BEDROOMS AND CLOSE |
| | PROXIMITY OF STAIRWAYS. 2-5.2.1.3 |
| | 3'FT FROM BATHS/KITCHENS.2-5.2.1.6 |
| | |
| | NOTE THAT THE KITCHEN IS LABELED AS |
| | "EXISTING BEDROOM". |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | PREVIOUS NOTES ARE ATTACHED. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |