| 2003-11-06 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | 1} PLEASE NOTE THAT ALL PLANS THAT ARE |
| | SIGNED AND SEALED BY AN ENGINEER ARE |
| | REQUIRED PER 61G15-23.002 FAC TO HAVE A |
| | TITLE BLOCK COMPLYING WITH SAID |
| | ARTICLE.THIS HAS BEEN AN ISSUE ON |
| | PREVIOUS PLANS THAT WERE SUBMITTED FOR |
| | REVIEW.WE ARE RETAINING A SET OF PLANS |
| | TO BE FILED AND TURNED INTO THE FBPE |
| | FOR DISCIPLINARY ACTION. |
| | |
| | 2} NOTE THAT THE LOAD CALCULATIONS MUST |
| | BE AS PER 230.31(B) WHEN USING THE |
| | OPTIONAL METHOD FOR AN EXISTING |
| | RESIDENCE. |
| | |
| | 3} THE AIC RATING ON THE PANEL IS 10000 |
| | AND THE NOTE ON THE RISER INDICATES |
| | 22000. PLEASE CLARIFY. |
| | |
| | 4} THE NOTE INDICATING SMOKE DETECTORS |
| | BEING FED FROM KITCHEN OR BATH CIRCUITS |
| | DOES NOT COMPLY WITH ART.210.12 2002 |
| | NEC. MUST BE ARC FAULT PROTECTED IN THE |
| | BEDROOMS. |
| | |
| | 5} THE REFERENCE TO "SPARK ARRESTOR"IS |
| | INCORRECT AND NOT IN COMPLIANCE WITH |
| | 210.12. |
| | |
| | 6} PLEASE NOTE KITCHEN COUNTER- |
| | -SPACE RECEPT SPACING SHALL MEET ART; |
| | 210-52C 1,2,3,4,AND 5,AND GFI PER |
| | 210.8(A)(6),INDICATE SAME ON PLANS. |
| | |
| | 7} PLEASE LIST THE REQ`D BATH(S) |
| | CIRCUIT(S). PER 210.11.(C)(3). |
| | MUST BE 20A AND #12AWG. |
| | |
| | 8} PLEASE NOTE FRONT AND REAR |
| | RECEPTS REQ`D PER 210.52E |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |