2003-11-06 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 1} PLEASE NOTE THAT ALL PLANS THAT ARE
 SIGNED AND SEALED BY AN ENGINEER ARE
 REQUIRED PER 61G15-23.002 FAC TO HAVE A
 TITLE BLOCK COMPLYING WITH SAID
 ARTICLE.THIS HAS BEEN AN ISSUE ON
 PREVIOUS PLANS THAT WERE SUBMITTED FOR
 REVIEW.WE ARE RETAINING A SET OF PLANS
 TO BE FILED AND TURNED INTO THE FBPE
 FOR DISCIPLINARY ACTION.
  
 2} NOTE THAT THE LOAD CALCULATIONS MUST
 BE AS PER 230.31(B) WHEN USING THE
 OPTIONAL METHOD FOR AN EXISTING
 RESIDENCE.
  
 3} THE AIC RATING ON THE PANEL IS 10000
 AND THE NOTE ON THE RISER INDICATES
 22000. PLEASE CLARIFY.
  
 4} THE NOTE INDICATING SMOKE DETECTORS
 BEING FED FROM KITCHEN OR BATH CIRCUITS
 DOES NOT COMPLY WITH ART.210.12 2002
 NEC. MUST BE ARC FAULT PROTECTED IN THE
 BEDROOMS.
  
 5} THE REFERENCE TO "SPARK ARRESTOR"IS
 INCORRECT AND NOT IN COMPLIANCE WITH
 210.12.
  
 6} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5,AND GFI PER
 210.8(A)(6),INDICATE SAME ON PLANS.
  
 7} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210.11.(C)(3).
 MUST BE 20A AND #12AWG.
  
 8} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210.52E
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718