| Plan Review Notes For Permit 03101794 |
| Permit Number |
03101794 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2004-02-04 00:00:00 | PLANS REVISED, DID NOT REVISE ORIG | | | REDLINES. | | | REDLINED PLANS FOR GROUNDING ELECTRODE | | | CONDUCTOR TO BE SIZED PER 250.66 #2 MIN | | | AND MISSING EQUIPMENT GROUNDING CONDUCT- | | | ORS BETWEEN MAINS AND PANELS. |
|