| 2004-01-07 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-MISSING ONE DWG A1 & A2. ONLY ONE COPY |
| | OF REVISED A1 AND A2 DWG WAS SUBMITTED |
| | 2-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 3-ARCHITECT TO PROVIDE ALL INFORMATION |
| | LISTED ON SEC. 1606.1.7 FBC 2001. |
| | 4-WHEN HAVING THE OPTION OF HAVING THE |
| | FIREPLACE, THEN ALL DETAILS & SPECS |
| | SHALL BE INCLUDED IN THE CONSTRUCTION |
| | DOCUMENTS. OTHERWISE, DELETE OPTION. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 5-LIVING ROOM AREA: PROVIDE COMPLETE |
| | SECTION/DETAIL AT COLUMN SHOWING HOW |
| | ARE WINDOWS GOING TO BE ATTACHED. |
| | **NOTE: CHECK WINDOW PRODUCT APPROVAL |
| | FOR REQUIRED SUBSTRATE. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | 6-PLANS NEED TO SPECIFY SAFETY GLASS AT |
| | LIVING ROOM WINDOWS. SEC. 2405.2 FBC. |
| | 7-PROVIDE FLORIDA PRODUCT APPROVAL FOR |
| | ENTRY DOOR WITH SIZE AS SHOWN ON PLAN. |
| | 8-ROOF TILE FASTENING SPECIFIED IS NOT |
| | ADEQUATE. SEE PRODUCT APPROVAL FOR MIN |
| | REQUIRED SIZES. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 9-RE-SUBMIT FLORIDA PRODUCT APPROVAL FOR |
| | A)"THERMA-TRU" ENTRY DOORS:*NEED SIZE AS |
| | SHOWN ON PLANS. **NO GOOD: PENDING FBC |
| | APPROVAL. ***NEED SWING OF DOOR AS |
| | SHOWN ON PLANS. ****SLIDING DOOR IS |
| | MISSING DRAWINGS AND IS PENDING FBC |
| | APPROVAL. NEED TO CHECK FOR SIZE AND |
| | SPECIFIC APPLICATION AS SHOWN ON PLANS |
| | B)GARAGE DOOR PRODUCT APPROVAL IS NOT |
| | APPROVED YET. IT'S APLIED FOR ONLY. |
| | C)IF USING FIXED WINDOWS BY "WINDSOR", |
| | THEN PROVIDE COMPLETE APPROVED DWGS & |
| | CHECK SIZES SHOWN ON PLANS. |
| | D)PGT PRODUCT APPROVAL PACKAGE: ONLY |
| | SUBMIT PRODUCT APPROVAL AND DRAWINGS |
| | FOR WINDOWS/DOORS, MULLIONS TO BE USED |
| | ON THIS PROJECT TO AVOID UNNECESSARY |
| | PAPERWORK. |
| | **NEED DRAWINGS FOR CASEMENT WINDOWS, |
| | WINDOW MULLIONS, FIXED WINDOWS (CHECK |
| | SIZES SHOWN ON PLANS) |
| | |
| | 10-NEED FL. PRODUCT APPROVAL FOR FRENCH |
| | DOORS. CHECK SIZE AND SWING. |
| | 11-PROVIDE UL LISTING AND COMPLETE SPECS |
| | FOR FIREPLACE AND BBQ AS REQ'D BY |
| | SECTIONS 2806 AND 2808 FBC 2001. |
| | 12-STORM SHUTTERS: A)PROVIDE 2 COPIES |
| | SIGNED,SEALED AS REQ'D BY ENGINEER. |
| | B)MEAN ROOF HEIGHT IS INCORRECT. |
| | C)ACCORDING TO INSTALLATION SCHEDULE |
| | SOME PANELS WILL ALLOW LESS THAN 2" |
| | EDGE DISTANCE. REVISE AS REQ'D. |
| | D)CLEARLY MARK ON ENGINEERED DRAWINGS |
| | SPECIFIC MOUNTING CONDITIONS & ANCHOR |
| | TYPE & SPACING TO BE USED ACCORDING TO |
| | THE DESIGN PRESSURES, EDGE DISTANCE, |
| | PANEL SPAN, CONNECTION TYPE AND STRUC- |
| | TURE TO BE ATTACHED TO (CONCRETE BLOCK |
| | OR CONCRETE). |
| | E)NEED TO INDICATE EMERGENCY EGRESS AS |
| | REQ'D BY SECTION 1005.4.5. EGRESS TO |
| | BE ACCESSIBLE FOR EVERYBODY WITHOUT |
| | GOING THRU ROOMS THAT MAY BE LOCKED. |
| | |
| | 13-CONTRACTOR SAID THAT HE WILL PROVIDE |
| | ADDITIONAL SOIL BORINGS AS REQ'D BY |
| | SOIL TEST REPORT. |
| | 14-PROVIDE FLORIDA PRODUCT APPROVAL FOR |
| | TRUSS ANCHORS. |
| | 15-REVISE ENERGY CALCULATIONS: A)UNDER |
| | ATTIC AREA IS INCORRECT. SEE SECTION |
| | 604.1.A.1 CHAPTER 13 FBC 2001. |
| | 16-REVISE TRUSS ANCHOR SCHEDULE: |
| | A)AVERAGE ULTIMATE TENSION CANN'T BE |
| | USED FOR DESIGN PURPOSES. SEE SIMPSON |
| | CONNECTOR HTT22. ALSO, CLARIFY WHAT |
| | ARE LATERAL FORCES F1 AND F2 TAKEN |
| | FROM. SEE CATALOGUE. |
| | **WHERE ARE LATERAL LOADS F1 & F2 TAKEN |
| | FROM?. PROVIDE ENGINEERING CALCS. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 17-CONTRACTOR TO UPDATE WORKERS COMP. |
| | |
| | |