| Plan Review Notes For Permit 03101791 |
| Permit Number |
03101791 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2004-11-18 00:00:00 | *********** UNSAT ********* | | | | | | 1)NOTE: PLEASE SEE 424.3B FOR MIN OCP | | | FOR AHU#2. | | | | | | 2)NOTE: PLEASE SEE 250.24, 250.6, NO | | | EQUIPMENT GROUNDING CONDUCTOR FROM METER | | | TO FIRST MEANS OF DISCONNECT. | | | | | | 3)NOTE: PLEASE SIZE GROUNDING ELECTRODE | | | CONDUCTOR PER 250.66 1/0 | | | | | | 4)NOTE: PLEASE SEE LOAD ON 1P20 BRKR FOR | | | FRIG. THIS IS SHOWN ON ONE CIRCUIT. | | | PLEASE NOTE: THIS IS THE SAME ON LOT | | | #17, BUT WAS NOT TYPED IN NOTES. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|