| Plan Review Notes For Permit 03101791 |
| Permit Number |
03101791 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2004-07-12 00:00:00 | *********** UNSAT **************** | | | | | | 1)NOTE: PLEASE CORRELATE PANELS AND | | | RISER DIAGRAM. PANEL SHOWN AS 150A AND | | | RISER SHOWS 200A'S. | | | | | | 2)NOTE: PELASE CORRELATE LOADS , AWG AND | | | OCP FOR A/C AHU'SETC. | | | PLEASE SEE 424.3B MIN OCP TO BE 125%. | | | | | | 3)NOTE: PLEASE SEE JACUZZI/WHIRLPOOL TUB | | | LISTED ON PANEL SCHEDULE BUT NOT SHOWN | | | ON PLANS. | | | | | | 4)NOTE: PLEASE SEE GENERAL NOTES TO | | | ELECTRICAL. PLEASE SEE NOTES #2 AND 4. | | | PLEASE ADJUST NOTES. | | | PLEASE SEE 210.12. | | | | | | 5 )NOTE: PLEASE SEE 220.3B4. | | | PLEASE SHOW ALL RECESSED LTS BASED ON | | | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT | | | BE FIGURED IN W/ 3W/PER SQ FT. | | | PLEASE PROVIDE FIXTURE INFORMATION ON | | | LEGEND. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | 2004-07-08 00:00:00 | NO ELECTRICAL REVISION SUBMITTED. |
|