| Plan Review Notes For Permit 03101791 |
| Permit Number |
03101791 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-12-22 00:00:00 | ********** NOTES REDLINED ************* | | | | | | 1)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTORS FROM MAINS TO | | | PANELS.250.122 | | | | | | 2)NOTE: PLEASE SEE OCP FOR AHU/HEAT | | | NEEDS TO BE SIZED PER 424.3B | | | | | | 3)NOTE: GROUNDING ELECTRODE CONDCUTOR | | | PER 250.66, MIN #2 | | | | | | PLEASE SEE THAT THE ABOVE HAS BEEN | | | REDLINED ON PLANS. PLEASE MAKE CORRECT- | | | -IONS ALONG W/ ANY REV'S. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|