| 2004-01-08 00:00:00 | DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE ENERGY CALCULATION FORM APPEARS |
| | TO CONTAIN ERRORS. THE CEILING AREA |
| | SHOULD BE MORE THAN THE FLOOR AREA DUE |
| | TO THE COFFERED CEILINGS IN SEVERAL OF |
| | THE ROOMS. SEE FBC CHAPTER 13 SECT.604. |
| | THE FORM LISTS THE R-VALUE OF THE FRAMED |
| | ADJACENT WALL AS R9. SHOULDN'T THIS BE |
| | R19 AT THE 2X6 WALL AND R11 AT THE 2X4 |
| | PORTION OF THE WALL? |
| | |
| | 3)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | SOME OF THIS INFORMATION IS NOT ON THE |
| | PLANS. |
| | |
| | 4) ON SHEET A5 THE D CONNECTION DETAIL |
| | IS INCORRECTLY SPECIFIED FOR THE GIRDER |
| | CONNECTION AT THE FRONT WALL OF BEDROOM. |
| | THERE IS NO COLUMN AT THIS LOCATION. |
| | |
| | 5) PLEASE REVISE THE ANCHOR SCHEDULE ON |
| | A5. ROWS G,H & I HAVE INCORRECT VALUES |
| | IN THE F1 AND F2 COLUMNS FOR LATERAL |
| | LOADS. NO LATERAL LOADS ARE GIVEN IN THE |
| | CATALOG FOR THESE CONNECTORS. THE |
| | ULTIMATE UPLIFT VALUE IS LISTED FOR THE |
| | SIMPSON HTT22 CONNECTOR. USE THE DESIGN |
| | VALUE WHICH INCLUDES A SAFETY FACTOR. |
| | |
| | 6) SPECIFY SAFETY GLASS FOR THE LIVING |
| | ROOM WINDOWS. SEE FBC 2405.2.1(4). |
| | |
| | 7) INDICATE HOW THE WINDOWS/BUCKS ARE TO |
| | BE ATTACHED TO THE STEEL HEADER AND |
| | COLUMNS AT THE LIVING ROOM WINDOWS. |
| | |
| | 8) SUBMIT MANUFACTURER'S SPECS. AND UL |
| | LISTING INFORMATION FOR OPTIONAL BBQ IF |
| | IT WILL BE INSTALLED. |
| | |
| | 9) THE STORM PANEL KEY PLAN AND SCHEDULE |
| | CONTAINS SOME ERRORS. THE FRONT DOORS |
| | ARE SHOWN AS SOLID DOORS ON PLANS AND |
| | THEIR HEIGHT IS NINE FEET. THE GUEST |
| | ROOM DOOR IS IMPACT RESISTANT FOR EGRESS |
| | AND THE WRONG OPENING IS INDICATED ON |
| | THE KEY PLAN. OPENING #34 IS MARKED AS |
| | 24 ON THE KEY PLAN. CHECK OPENING SIZES |
| | AND SPANS. CLEARLY MARK ON THE |
| | ENGINEERED DRAWINGS THE SPECIFIC TYPE OF |
| | MOUNTI, THE ANCHOR TYPE AND SPACING |
| | BASED ON DESIGN PRESSURES, EDGE DISTANCE |
| | PLANEL SPAN, ETC. |
| | |
| | 10) PLEASE ATTACH THE COVER SHEETS FROM |
| | THE STATE PRODUCT APPROVALS TO THE |
| | APPROPRIATE DRAWINGS FOR THAT SPECIFIC |
| | ITEM (WINDOW, DOOR, ETC.). ONLY SUBMIT |
| | PRODUCT APPROVALS FOR ITEMS THAT WILL BE |
| | USED IN THIS PROJECT. |
| | |
| | 11) SUBMIT INSTALLATION DRAWINGS FOR THE |
| | FIXED WINDOWS. ONLY THE STATE COVERSHEET |
| | WAS SUBMITTED. |
| | |
| | 12) SUBMIT DRAWINGS FOR THE CASEMENT |
| | WINDOWS. ONLY STATE COVERSHEET SUBMITTED |
| | |
| | 13) SUBMIT DRAWINGS FOR THE MULLIONS. |
| | |
| | 14) THERE ARE NO STOREFRONT DOORS SHOWN |
| | ON THE PLANS. REMOVE THESE FROM THE |
| | SUBMITTAL OR SHOW THEIR LOCATION ON THE |
| | PLANS. |
| | |
| | 15) SUBMIT PRODUCT APPROVALS FOR THE |
| | SINGLE AND DOUBLE FRENCH DOORS. |
| | |
| | 16) DOUBLE HUNG AND HORIZONTAL SLIDING |
| | WINDOWS ARE NOT SHOWN ON THE PLANS. |
| | REMOVE THESE PRODUCT APP. FROM SUBMITTAL |
| | |
| | 17) SUBMIT PRODUCT APPROVALS FOR BUTT |
| | GLASS WINDOW. SEE FBC 2406.2. |
| | |
| | 18) SUBMIT PRODUCT APPROVALS FOR DOUBLE |
| | OUTSWING 9' HIGH ENTRY DOORS. |
| | |
| | 19) CONTRACTOR'S WORKERS COMP. MUST BE |
| | UPDATED BEFORE PERMIT WILL BE ISSUED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |