| 2003-11-06 00:00:00 | ************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SIZE SEC'S PER 310.16 |
| | OR 310.15B6 FOR A MIN. |
| | SHOWS 1/0'SFOR 200A'S? |
| | |
| | 2)NOTE: PLEASE SEE THE GEC TO FOOTER |
| | STEEL SHOULD BE SIZE PER 250.66. |
| | THE #2 SHOWN SEEMS TO BE REVERSED WITH |
| | THE # 4.. |
| | |
| | 3)NOTE: PLEASE SEE THAT WE ARE UNDER THE |
| | 2002 NEC AND 210.12 HAS CHANGED FROM |
| | WHAT IS NOTED ON PLANS FOR ARC FAULT. |
| | PLEASE LIST THE REQ'D ARC FAULT PROTECT- |
| | -ED CIRCUITS ON PANEL SCHEDULE. |
| | 210.12 |
| | |
| | 4)NOTE: PLEASE SEE 210.52 FOR RECEPT |
| | SPACING, THERE ARE A FEW MISSING. |
| | |
| | 5)NOTE: PLEASE SEE 210.63 FOR REQ'D |
| | GFI RECEPT FOR A/C COND UNITS. |
| | |
| | 6)NOTE: PLEASE SEE 210.52D FOR RECEPT |
| | SPACING FROM SINKS/LAV. |
| | |
| | 7)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS |
| | ON PLANS FOR ALL ROOMS. |
| | |
| | 8)NOTE: PLEASE SEE MISSING SD FOR WHAT |
| | APPEARS TO BE A BEDROOM/ADAPTABLE BEDRM |
| | PER NFPA-72 8-1.4.2. SD IS ALSO REQ'D |
| | TO BE INSIDE BEDROOM(MASTER?). |
| | |
| | 9)NOTE: PLEASE SEE PLANS, DOES NOT SHOW |
| | MAIN DISCONNECT NEXT TO METER? |
| | 215.5 |
| | |
| | 10)NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | ED. 210.8.A6 |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | INSERT NEW SHEETS INTO TWO COMPLETE SETS |
| | FOR REVIEW AND STAMPING. IF THERE ARE |
| | ANY QUESTIONS, PLEASE CALL. |
| | |