| 2003-12-01 00:00:00 | UNSAT |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) ON SHEET A3 THE C8 COLUMN IS NOT |
| | LISTED IN THE COLUMN SCHEDULE. |
| | |
| | 3) SAFETY GLAZING IS REQUIRED IN WINDOWS |
| | THAT ARE WITHIN 3' HORIZONTALLY OF A TUB |
| | OR SHOWER. SEE FBC 2405.2. SPECIFY ON |
| | PLANS. |
| | |
| | 4) INSULATED OR SOLID CORE DOORS ARE |
| | REQUIRED BETWEEN THE GARAGES AND THE |
| | CONDITIONED SPACE PER FBC CHAPTER 13. |
| | SPECIFY ON PLANS. |
| | |
| | 5) SPECIFY THE SIZE OF THE ATTIC ACCESS |
| | IN HER CLOSET. SEE FBC 2309.6. |
| | |
| | 6)SPECIFY THE ATTIC ACCESS FOR SERVICING |
| | OF THE AHU IN ATTIC OF GOLF CART GARAGE. |
| | SEE FBC MECHANICAL 306.3. CLARIFY THE |
| | LOCATION OF THIS UNIT. THE ROOF FRAMING |
| | PLAN INDICATES THAT IT IS HUNG FROM THE |
| | TRUSSES AND NOT IN THE ATTIC. |
| | |
| | 7) SUBMIT MANUFACTURER'S SPECS. AND UL |
| | LISTING INFORMATION FOR THE BBQ ON THE |
| | LANAI. |
| | |
| | 8) THE ROOF FRAMING PLAN ON A5 SPECIFIES |
| | DETAILS B,C & D ON A4. THESE DETAILS ARE |
| | ON SHEET A5 AND ARE INCORRECTLY LABELED |
| | AS A4. PLEASE CORRECT. |
| | |
| | 9) THE STEEL COLUMN CAPS HAVE THE WRONG |
| | CONFIGURATIONS SPECIFIED AT SEVERAL |
| | LOCATIONS. HANGERS ARE INDICATED AT STL. |
| | COLUMNS AND CAPS ARE SPECIFIED WHERE |
| | THERE ISN,T A COLUMN. SEE SHEET A5 AND |
| | DETAILS ON A5. |
| | |
| | 10) PROVIDE DETAILS FOR THE 3"X 6" TUBE |
| | STEEL COLUMN BASES AND CAPS. |
| | |
| | 11) SOME OF THE GIRDERS DO NOT HAVE A |
| | CONNECTOR SPECIFIED. SEE THE NOTES ON |
| | A5. |
| | |
| | 12) THE NOTE ON THE WALL SECTION ON A8 |
| | EXCLUDES SOFFIT VENTS AT CROWN FACIA |
| | AREAS. SPECIFY THAT ATTIC VENTS SHALL |
| | PROVIDE A NET FREE VENT AREA WITH A |
| | RATIO OF 1/150 OF CEILING AREA. SEE FBC |
| | 2309.7. |
| | |
| | 13) PLEASE UPDATE THE REFERENCE TO THE |
| | SBC 97 TO THE 2001 FBC ON A8. ALSO |
| | UPDATE THE SPECIFIED HUGHES CONNECTOR TO |
| | A CURRENT CONNECTOR. HUGHES IS NO LONGER |
| | IN BUSINESS. |
| | |
| | 14) CORRECT THE R VALUES LISTED ON THE |
| | ENERGY CALCULATION FORM. THE CEILING |
| | INSULATION IS R30 ON THE PLANS. THE R |
| | VALUE OF THE INSULATION AT THE CMU |
| | EXTERIOR WALLS IS 4.2. THE ADJACENT |
| | FRAME WALL SHOULD BE R-19 FOR 2X6 OR |
| | R-11 FOR 2X4 WALLS. |
| | |
| | 15) CHANGE THE R VALUE OF THE INSULATION |
| | AT THE ATTIC ACCESS DETAIL ON A9 TO |
| | R-30 TO CORRESPOND WITH THE WALL SECTION |
| | ON A8. |
| | |
| | 16) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. |
| | |
| | 17) SUBMIT ENGINEERING FOR BUTT GLASS |
| | WINDOW PER FBC 2406.2. |
| | |
| | 18) SUBMIT PRODUCT APPROVALS FOR FIXED |
| | GLASS, ARCHED FIXED GLASS AND CASEMENT |
| | WINDOWS, STRUCTURAL MULLIONS, OUTSWING |
| | ENTRY DOORS AND STORM PANELS. |
| | |
| | 19) SUBMIT THE APPROVED DRAWINGS FOR THE |
| | OVERHEAD GARAGE DOORS. |
| | |
| | 20) PLEASE CLARIFY WHERE THE ALUMINUM |
| | STOREFRONT DOORS WILL BE INSTALLED. |
| | NOTE THE LIMITATION ON THE PRODUCT |
| | APPROVAL FOR WATER INTRUSION WITHOUT AN |
| | ADEQUATE OVERHANG. |
| | |
| | 21) PRODUCT APPROVALS FOR IMPACT AND |
| | NON-IMPACT RESISTANT SH WINDOWS AND |
| | STOREFRONT DOORS WERE SUBMITTED. PLEASE |
| | CLARIFY. |
| | |
| | 22)FBC 1005.4.5 (GLITCH AMENDMENTS |
| | JULY 1, 2003) REQUIRES AT LEAST ONE |
| | MEANS OF ESCAPE FROM A DWELLING WHEN |
| | SHUTTERED FOR IMPACT PROTECTION. THE |
| | MEANS OF ESCAPE SHALL BE WITHIN THE |
| | FIRST FLOOR OF THE DWELLING AND CAN NOT |
| | BE LOCATED IN A GARAGE. OCCUPANTS IN ANY |
| | PART OF THE DWELLING SHALL HAVE ACCESS |
| | TO IT WITHOUT HAVING TO PASS THROUGH A |
| | LOCKABLE DOOR NOT UNDER THEIR CONTROL. |
| | INDICATE HOW COMPLIANCE WILL BE |
| | ACHIEVED AT THE OPTIONAL GUEST SUITE. |
| | THE KEY PLAN INDICATES IMPACT GLASS FOR |
| | EGRESS AT THE WRONG LOCATION. |
| | |
| | IN ORDER TO EXPEDITE PLAN REVIEW, PLEASE |
| | RETURN OLD PLANS WITH RESUBMITTAL. |