Plan Review Notes
Plan Review Notes For Permit 03101790
Permit Number 03101790
Review Stop M
Sequence Number 1
Notes
Date Text
2003-11-24 00:00:00DENIED:
 1.PLANS VAGUE AS TO THE SCOPE OF HVAC
 WORK.
  
 2.PLEASE PROVIDE REVISED OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) 403.3.
  
 3.PLEASE INDICATE EXISTING SYSTEM.
 RTU, AHU, VAV'S?
  
 4.INDICATE IF RETURN IS A DUCTED OR
 PLENUM.NO COMBUSTIBLES ABOVE THE
 CEILING IN THE RETURN AIR PLENUM PER
 2001 FBC(M) 602.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.