| Plan Review Notes For Permit 03101790 |
| Permit Number |
03101790 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-11-24 00:00:00 | DENIED: | | | 1.PLANS VAGUE AS TO THE SCOPE OF HVAC | | | WORK. | | | | | | 2.PLEASE PROVIDE REVISED OUTSIDE AIR | | | CALCULATIONS PER 2001 FBC(M) 403.3. | | | | | | 3.PLEASE INDICATE EXISTING SYSTEM. | | | RTU, AHU, VAV'S? | | | | | | 4.INDICATE IF RETURN IS A DUCTED OR | | | PLENUM.NO COMBUSTIBLES ABOVE THE | | | CEILING IN THE RETURN AIR PLENUM PER | | | 2001 FBC(M) 602.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|