2003-11-26 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 03101790
 ADD: 319 CLEMATIS STREET
 CONT: CABOT
 TEL: (561)601-8848
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A102 DETAIL# 3 INDICATES THE USE
 OF SOFFITS, THE ATTACHMENT TO THE STRUC-
 TURE ABOVE NOT GIVEN NOR THE CENTER/
 CENTER FOR STEEL STUDS.
  
 3) NOTE : TYPE II BUILDING ALL BACKING
 TO BE FIRE RETARDENT TREATED,609.2.1
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715