| Plan Review Notes For Permit 03101736 |
| Permit Number |
03101736 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-03-18 00:00:00 | DENIED | | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | FLORIDA STATUTES. | | | FBC-2001 CHAPTER 1 | | | | | | 1) ALL CHANGES TO A SIGNED AND SEALED | | | SET OF PLANS SHALL BE SIGNED AND DATED | | | BY ENGINEER OF RECORD. | | | 2) HEATER IS STILL SHOWN ON POOL PIPING | | | SCHEMATIC. PIPING SCHEMATIC SHALL RE- | | | FLECT THE POOL SPECIFICATIONS AND POOL | | | LAYOUT. SECTION 104.2.1 | | | 3) INFORMATIONAL - ALL POOL WORK SHALL | | | NOT COMMENCE UNTIL AN RPZV BACKFLOW IS | | | INSTALLED AND INSPECTED. SEPARATE PERMIT | | | REQUIRED BY LICENSED PLUMBING CONTRACTOR | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|