| 2003-12-24 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-LOAD SCHEDULE: ADD ATTIC LIVE LOAD OF |
| | 30PSF OR 10PSF AS REQUIRED BY TABLE |
| | 1604.1 FBC 2001. |
| | **NOTE: ATTIC LIVE LOAD IS CONCURRENT |
| | WITH ROOF LIVE LOAD. |
| | 2-PROVIDE COMPLETE INFORMATION FOR STORM |
| | SHUTTERS: A)NEED FLORIDA PRODUCT |
| | APPROVAL OR SITE SPECIFIC ENGINEERING. |
| | B)PROVIDE KEY PLAN & COMPLETE INSTALLA- |
| | TION SCHEDULE. |
| | C)CLEARLY MARK ON DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS & ANCHOR TYPE AND |
| | SPACING TO BE USED. |
| | |
| | 3-PROVIDE COMPLETE SOIL TEST REPORT THAT |
| | SHOWS SOIL PREPARATION & SOIL BEARING |
| | CAPACITY. SECTION 1804.2.2 OF CITY |
| | AMENDMENTS TO FBC 2001. |
| | 4-PROVIDE FLORIDA PRODUCT APPROVAL OR |
| | SITE SPECIFIC ENGINEERING FOR ROOF |
| | TILE, ALL TYPES OF DOORS AND WINDOWS |
| | AS SHOWN ON PLANS, WINDOW MULLIONS. |
| | **NOTE: SEE WWW.FLORIDABUILDING.ORG FOR |
| | REQUIRED INFORMATION TO BE SUBMITTED. |
| | 5-ARCHITECT TO SPECIFY ROOF TILE FASTE- |
| | NING AS REQUIRED BY SECTION 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | 6-PROVIDE SPECIFICATIONS FOR ANCHORING |
| | GABLE END TRUSS. INFORMATION IS NOT |
| | GIVEN ON THE ROOF FRAMING PLAN, TRUSS |
| | ANCHOR SCHEDULE OR DETAIL 7/A6.SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT 805-6712. |