2003-11-21 00:00:00BUILDING REVIEW CHECKLIST:
 1-LOAD SCHEDULE: ADD THE ATTIC LIVE LOAD
 AS REQUIRED BY TABLE 1604.1 FBC 2001.
 **NOTE: ADD 30PSF LIVE LOAD FOR ATTIC
 WITH STORAGE AND 10PSF W/O STORAGE.
 2-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS: A)NEED FLORIDA PRODUCT
 APPROVAL OR SITE SPECIFIC ENGINEERING.
 B)PROVIDE KEY PLAN AND COMPLETE INSTA-
 LLATION SCHEDULE.
 C)CLEARLY MARK ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS & ANCHOR TYPE AND
 SPACING TO BE USED.
  
 3-PROVIDE COMPLETE SOIL TEST REPORT WITH
 SOIL BEARING INFORMATION AND SOIL PRE-
 PARATION RECOMMENDATIONS. SECTION
 1804.2.2 CITY AMENDMENTS TO FBC 2001.
 4-PROVIDE FLORIDA PRODUCT APPROVAL OR
 SITE SPECIFIC ENGINEERING FOR ROOF
 TILE, ALL TYPES OF DOORS AND WINDOWS,
 WINDOW MULLIONS AS SHOWN ON PLANS AS
 REQ'D BY FBC AS OF OCTOBER 1ST 2003.
 **SEE WWW FLORIDABUILDING.ORG.
  
 **NOTES:
 * NEED ENTRY DOOR W/SIDELITE AS SHOWN ON
 PLANS.
 * MAKE SURE INFORMATION PROVIDED IS NOT
 EXPIRED.
 * ONLY SUBMIT INFORMATION FOR ITEMS THAT
 APPLY TO THIS HOUSE TO REDUCE PAPER
 WORK AND UNNECESSARY REVIEWS.
  
 5-SPECIFY FASTENING REQUIREMENTS FOR
 ROOF TILE. SEE SECTION 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
 6-OWES $22.08 FOR UPDATED VALUATION. SEE
 ATTACHED RECEIPT.
 7-SHEET A-2: RAKE BEAM DETAIL 3/A2 DOES
 NOT MATCH SPECIFICATIONS SHOWN ON
 TIE-BEAM SCHEDULE. REVISE/CLARIFY AS
 REQ'D. SEC. 104.2.1.2 CITY AMENDMENTS.
 8-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS FOR COMMENTS AND SECTION
 2405.2 FBC 2001.
 9-PROVIDE SPECIFICATIONS FOR ANCHORING
 GABLE END TRUSS. DETAIL 7/A6 SEND YOU
 TO THE CONNECTOR SCHEDULE, BUT THERE
 ARE NOT SPECS ON THE SCHEDULE FOR
 GABLE END TRUSSES. NEITHER ON THE ROOF
 FRAMING PLAN. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.