| Plan Review Notes For Permit 03101696 |
| Permit Number |
03101696 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-11-05 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | TOTHE PLANS AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE NOTE THAT ALL PLANS | | | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- | | | ING A TITLE BLOCK, MUST BE SIGNED, | | | DATED AND SEALED BY THE ARCH/ENGINEER OF | | | RECORD. PER FS/FAC 481.221 & 471.025. | | | SEE SHEET E-2. | | | | | | 2} PLEASE SEE NOTES ON PLANS REGARDING | | | HOW THE SMOKE DETECTORS ARE FED.SHEET | | | E-1 SHOWS THEM BEING FED FROM A KITCHEN | | | OR BATHROOM LIGHT CIRCUIT.NOTE #14 ON | | | E-2 SAYS THE SAME THING.PLEASE NOTE | | | THAT NFPA-70 (NEC) 2002 EDITION | | | REQUIRES THESE AND ALL "OUTLETS" (SEE | | | DEFINITION IN NEC),BE PROTECTED BY ARC | | | FAULT CIRCUIT INTERUPTERS. SEE210.12(B). | | | PLEASE CHANGE THIS WORDING ON ALL | | | FUTURE PLANS,ALL MODELS.THANKS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|