| 2004-01-14 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 12/3/03: |
| | |
| | 6) SHEET 3, TRUSS ANCHORAGE SCHEDULE. |
| | TRUSS ANCHORAGE NOTE #3 STATES THAT |
| | TRUSS ANCHORAGE SPECIFICATION WILL BE |
| | PROVIDED WITH THE TRUSS SHOP DRAWINGS. |
| | THAT PROPOSAL IS NOTED, BUT A PERMIT |
| | CANNOT BE ISSUED UNTIL THE PLANS SPECIFY |
| | VALID ANCHORS (MANUFACTURER AND REF.) |
| | AND SHOW THOSE ANCHORS TO HAVE UPLIFT |
| | CAPACITY IN EXCESS OF THE CALCULATED |
| | UPLIFT. |
| | |
| | 7) FL. ADMIN CODE RULE 9B-72. |
| | A SEARCH AT THE DEPT OF COMMUNITY |
| | AFFAIRS PRODUCT APPROVAL WEBSITE |
| | WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP |
| | SHOWS NO MATCHING STATEWIDE PRODUCT |
| | APPROVAL FOR EITHER OF THE TWO PROPOSED |
| | OUTSWING COMMERCIAL STEEL DOORS (IMPACT) |
| | BY FIREDOOR CORPORATION OF FLORIDA. |
| | - FOR EXAMPLE, REFER TO THE STATEWIDE |
| | PRODUCT APPROVAL LISTING PRINTED AND |
| | ADDED TO THE ASPHALT SHINGLE SUBMITTAL - |
| | SPECIFY ALTERNATIVE DOORS THAT HAVE |
| | STATEWIDE OR LOCAL PRODUCT APPROVAL. |
| | ALSO, NOTE THAT DRAWING SHEETS 1 THRO' 5 |
| | OF 5 ARE MISSING FROM BOTH OF THE |
| | SUBMITTED MIAMI-DADE NOA'S. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |