| Plan Review Notes For Permit 03101552 |
| Permit Number |
03101552 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-11-05 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLORIDA ADMINISTRATIVE CODE | | | | | | 1) SHT 1 OF 3 REST ROOM ELEVATION VIEW | | | "A". A WATER CLOSET SHALL NOT BE SET | | | CLOSER THAN 30" CENTER TO CENTER BETWEEN | | | TOILETS OR ADJACENT FIXTURES. 405.3.1 | | | 2) SHT 1 OF 3 HOSE BIBB DETAIL. AIR | | | CHAMBERS NOT APPROVED. DELETE FROM | | | DETAIL. 604.9 | | | 3) SHT 2 OF 3 WATER ISOMETRIC. AIR | | | CHAMBERS ARE NOT APPROVED. DELETE FROM | | | ISOMETRIC. 604.9 | | | 4) SHT 1 OF 1 IRRIGATION PLAN. A TITLE | | | BLOCK MUST APPEAR ON ALL ARCHITECTURAL | | | DRAWINGS. 61G1-16.004. (SEE ATTACHED | | | SHEET FOR REFERENCE). | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|