2003-11-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
  
 1) SHT 1 OF 3 REST ROOM ELEVATION VIEW
 "A". A WATER CLOSET SHALL NOT BE SET
 CLOSER THAN 30" CENTER TO CENTER BETWEEN
 TOILETS OR ADJACENT FIXTURES. 405.3.1
 2) SHT 1 OF 3 HOSE BIBB DETAIL. AIR
 CHAMBERS NOT APPROVED. DELETE FROM
 DETAIL. 604.9
 3) SHT 2 OF 3 WATER ISOMETRIC. AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 ISOMETRIC. 604.9
 4) SHT 1 OF 1 IRRIGATION PLAN. A TITLE
 BLOCK MUST APPEAR ON ALL ARCHITECTURAL
 DRAWINGS. 61G1-16.004. (SEE ATTACHED
 SHEET FOR REFERENCE).
  