| Date |
Text |
| 2003-11-18 00:00:00 | UNSAT |
| | |
| | 1) THE UPLIFT VALUES LISTED IN THE |
| | CONCRETE TO TRUSS CONNECTOR SCHEDULE ON |
| | SHEET A5A ARE INCORRECT FOR MULTIPLE |
| | STRAPS. THE VALUES DO NOT DOUBLE FOR 2 |
| | STRAPS OR TRIPLE FOR THREE DUE TO THE |
| | PROXIMITY OF THE STRAPS AND CONE PULLOUT |
| | OF THE CONCRETE. SEE THE SIMPSON CATALOG |
| | EXAMPLE: (2) HETA 20 STRAPS EMBEDDED IN |
| | A CONCRETE TIE BEAM HAS A UPLIFT VALUE |
| | OF 2710# NOT 3030# LISTED IN THE SCHED. |
| | ON THE PLANS. PLEASE REVISE. |
| | |
| | 2) PROVIDE A DETAIL INDICATING THE |
| | ATTACHMENT OF THE WOOD FRAME INTERIOR |
| | BEARING WALLS TO THE EXTERIOR MASONRY OR |
| | CONCRETE WALLS. |
| | |
| | 3) AN (A5) CONCRETE TO TRUSS CONNECTOR |
| | IS INCORRECTLY SPECIFIED AT THE WOOD |
| | FRAME INTERIOR BEARING WALL AT THE |
| | DINING ROOM ON SHEET A5A. PLEASE CORRECT |
| | |
| | 4) ON SHEET A5A SECTION 11 ON A8 IS |
| | INDICATED AT THE INTERIOR KITCHEN WALL. |
| | PLEASE CLARIFY. |
| | |
| | 5) PROVIDE (2) PRODUCT APPROVALS, KEY |
| | PLANS AND INSTALLATION SCHEDULES |
| | INDICATING THE SPECIFIC TYPES OF ANCHORS |
| | TO BE USED FOR STORM PANELS. A SEPARATE |
| | PERMIT WILL BE REQUIRED IF NOT SUBMITTED |
| | AT THIS TIME. |
| | |
| | 6) PRODUCT APPROVALS FOR APPLICATIONS |
| | SUBMITTED AFTER OCTOBER 1, 2003 ARE |
| | REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCT WITH |
| | STATE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT A COMPLETED |
| | APPLICATION FOR LOCAL PRODUCT APPROVAL |
| | PER RULE 9B-72. SEE ATTACHMENT. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |