| Plan Review Notes For Permit 03101412 |
| Permit Number |
03101412 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-11-06 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED | | | PRIOR TO, DURING AND AFTER CONSTRUCTION. | | | | | | 2) SUITABLE ROADS ARE TO BE PROVIDED | | | FOR FIRE AND PARAMEDICAL ACCESS | | | DURING CONSTRUCTION. | | | | | | 3) SEPARATE PLANS AND PERMITS | | | REQUIRED FOR ENTRY GATES. WHAT | | | PROVISIONS WILL BE MADE FOR FIRE | | | AND PARAMEDICAL ACCESS. WHAT HAPPENS | | | WHEN LOSS OF POWER OCCURS. WILL THE | | | GATEHOUSE BE STAFFED FULL TIME OR | | | PART TIME. | | | | | | 4) TAMPER SWITCHES, CHAINS AND LOCKS | | | ARE REQUIRED ON FIRE LINE BACKFLOW | | | DEVICE. | | | | | | 5) FIRE HYDRANTS SHALL HAVE A MINIMUM | | | CLEARANCE OF 7'-6" TO THE FRONT AND | | | SIDES OF THEM. A MINIMUM OF 4' | | | CLEARANCE IS REQUIRED TO THE REAR OF | | | THEM. | | | | | | 6) IT APPEARS THAT ADDITIONAL FIRE | | | HYDRANTS MAY BE NEEDED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|