2003-11-06 00:00:001) WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
  
 2) SUITABLE ROADS ARE TO BE PROVIDED
 FOR FIRE AND PARAMEDICAL ACCESS
 DURING CONSTRUCTION.
  
 3) SEPARATE PLANS AND PERMITS
 REQUIRED FOR ENTRY GATES. WHAT
 PROVISIONS WILL BE MADE FOR FIRE
 AND PARAMEDICAL ACCESS. WHAT HAPPENS
 WHEN LOSS OF POWER OCCURS. WILL THE
 GATEHOUSE BE STAFFED FULL TIME OR
 PART TIME.
  
 4) TAMPER SWITCHES, CHAINS AND LOCKS
 ARE REQUIRED ON FIRE LINE BACKFLOW
 DEVICE.
  
 5) FIRE HYDRANTS SHALL HAVE A MINIMUM
 CLEARANCE OF 7'-6" TO THE FRONT AND
 SIDES OF THEM. A MINIMUM OF 4'
 CLEARANCE IS REQUIRED TO THE REAR OF
 THEM.
  
 6) IT APPEARS THAT ADDITIONAL FIRE
 HYDRANTS MAY BE NEEDED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910