| 2003-11-03 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03101403 |
| | ADD: 310 EVERNIA |
| | CONT: HEDRICK BROTHERS |
| | TEL: (561)689-8880 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-1 INDICATES THAT THIS BUILD- |
| | ING IS TO BE FIRE SPRINKLERED, BUT NO |
| | PLANS WERE SUBMITTED? |
| | |
| | 2) DUCTWORK IN STAIRWELL: 1006.1.3.1. |
| | PENETRATIONS INTO AND OPENINGS THROUGH A |
| | STAIRWAY ENCLOSURE ASSEMBLY ARE PROHIBIT |
| | ED EXCEPT FOR REQUIRED EXIT DOORS, DUCT- |
| | WORK AND EQUIPMENT NECESSARY FOR INDEPEN |
| | DENT STAIR PRESSURIZATION, SPRINKLER |
| | PIPING, STANDPIPES AND ELECTRICAL CON- |
| | DUIT SERVING THE STAIRWAY AND TERMINAT- |
| | ING AT A STEEL BOX NOT EXCEEDING 16 SQ |
| | INCHES. |
| | |
| | 3) FOAM COLUMNS AND PILASTERS: 803.4 |
| | FOAM PLASTIC TRIM SHALL NOT BE FOR TRIM, |
| | SEE EXCEPTIONS! PROVIDE ADDITIONAL INFOR |
| | MATION. |
| | |
| | 4)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | STAIRS RISE & RUN GUARDRAILS, HANDRAILS |
| | AND EXTENSIONS. |
| | |
| | 5)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | AC-1 INDICATES A SKYLIGHT IS THIS EXIST- |
| | ING OR IS IT NEW? |
| | |
| | 6) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORT, SBCCI OR DADE COUNTY |
| | REPORT ARE ACCEPTED. MISSING REPORT: |
| | A) FRENCH DOORS/ STORM SHUTTERS |
| | |
| | 7) TABLE 803.3 MINIMUM INTERIOR FINISH |
| | CLASSIFICATION; PROVIDE INFORMATION |
| | BASED ON INTERIOR FINISH REQUIREMENTS |
| | BASED ON OCCUPANCY |
| | |
| | 8)1511.7 ROOF MOUNTED MECHANICAL UNIT |
| | S SHALL BE MOUNTED ON CURBS RAISED A |
| | MINIMUM OF 8 INCHES ABOVE THE ROOF SUR- |
| | FACE, OR WHERE ROOFING MATERIALS EXTEND |
| | BENEATH THE UNIT, ON RAISED EQUIPMENT |
| | SUPPORTS PROVIDING A MINIMUM CLEARENCE |
| | HEIGHT IN ACCORDANCE WITH TABLE 1511.7. |
| | MECH. 301.13 WIND RESISTANCE |
| | MECHANICAL EQUIPMENT, APPLIANCES AND SUP |
| | PORTS THAT ARE EXPOSED TO WIND SHALL BE |
| | DESIGNED AND INSTALLED TO RESIST THE |
| | WIND PRESSURES ON THE EQUIPMENT & THE |
| | SUPPORTS AS DETERMINED IN ACCORDANCE |
| | WITH THE FL BLD CODE. THIS MAY BE ACCOMP |
| | LISHED BY DESIGN OR BY APPLICATION OF |
| | SECTION 301.13.1. |
| | |