| 2003-11-04 00:00:00 | PLAN DENIED | | | 1) REFER TO SECTION 601.4 F.B.C (M) | | | BALANCED RETURN AIR.NEW CODE WENT | | | INTO EFFECT JULY 1 2003. | | | 2) REFER TO SECTION 307.2.3 AUXILLIARY | | | DRAIN PANS.AUXILLIARY DRAIN PANS | | | SHALL BE INSTALLED UNDER ALL COILS | | | ON WHICH CONDENSATION WILL OCCUR. | | | PLAN REVIEW BY HAROLD MOSER | | | (561)805-6732 |
|