| Plan Review Notes For Permit 03101347 |
| Permit Number |
03101347 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-11-05 00:00:00 | ****BUILDING PLAN REVIEW FAILED******** | | | | | | 1. PLANS MUST BE ORIGINAL WITH SIGNED & | | | SEALED PLANS. CANNOT USE PLANS THAT | | | HAVEPHOTO COPIED APPROVALS FROM | | | PREVIOUS HOUSES. SUBMIT & BE SURE SEAL | | | IS READABLE. | | | | | | 2. TAKE PLANS TO PALM BEACH COUNTY & PAY | | | IMPACT FEES.HAVE PLANS STAMPED & | | | SUBMIT A COPY OF THE PAID RECEIPT. | | | | | | 3. THE PRODUCT APPROVAL FOR THE FIXED | | | WINDOWS HAS EXPIRED.SUBMIT UPDATED | | | PRODUCT APPROVAL. | | | | | | 4. PERMIT FEES HAVE BEEN ADJUSTED TO | | | REFLECT THE SQ. FT. THAT FEES ARE BASED | | | ON. | | | | | | 5.SUBMIT A COPY OF THE FIRST PAGE OF THE | | | FLORIDA ENERGY EFFICIENCY CODE. | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER. | | | 805-6713 |
|