| 2005-08-09 00:00:00 | ************* UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SEE EQUIPMENT GROUNDING |
| | NOT SHOWN FROM MAIN TO GUTTER, SUB |
| | PANELS. PLEASE SIZE PER 250.122. |
| | 250.110,250.24.250.118, LOCAL |
| | AMENDMENTS. |
| | PLEASE SEE PREVIOUS PLANS CALLED FOR |
| | EQUIPMENT GRNDS, HOWEVER THEY WERE |
| | REDLINED AS BEING WRONG SIZE. |
| | |
| | 2)NOTE: PLEASE SEE PLANS INDICATE "TWO" |
| | -SECTIONS FOR PANEL "T", PANEL SCHEDULE |
| | FOR PANEL "T" ALSO IS SHOWN AS 84 |
| | CIRCUITS, HOWEVER WHAT APPEARS TO BE |
| | ONLY ONE PANEL SCHEDULE, WITH 42 |
| | CIRCUITS WAS SUBMITTED? |
| | PLEASE CORRELATE. IF SECTION TWO TO |
| | PANEL "T" DOES NOT CONTAIN ANY OCP |
| | DEVICES OR CIRCUIT, PLEASE SHOW SEC TWO |
| | BLANK. IF INDEED THERE ARE CIRCUITS IN |
| | THIS PANEL, PLEASE SHOW. |
| | PLEASE ALSO SEE RISER SHOWS ONLY ONE |
| | PANEL SECTION FOR "T". |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE INDICATE ALL CIRCUITING |
| | ON PLANS AND CORRELATE WITH THE |
| | SUBMITTED PANEL SCHEDULE. |
| | PLEASE SEE EM/EXT LTS, 700.12E,THE |
| | BRANCH CIRCUIT FEEDING THE UNIT |
| | EQUIPMENT SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD |
| | OF ANY LOCAL SWITCHES. |
| | PLEASE SEE OTHER POSSIBLE LTS SHOWN ON |
| | PLANS WHICH DO NOT APPEAR TO SHOW ANY |
| | MEANS OF CONTROL OR CIRCUITS? |
| | THESE HAVE BEEN REDLINED ON ONE SET OF |
| | PLANS. |
| | |
| | PLEASE BE SURE TO SEE ANY POSSIBLE |
| | COMMENTS FROM OTHER REVIEWER(S) WHICH |
| | MAY AFFECT ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL THIS |
| | OFFICE. |
| | |