Plan Review Notes
Plan Review Notes For Permit 03101282
Permit Number 03101282
Review Stop E
Sequence Number 5
Notes
Date Text
2005-08-09 00:00:00************* UNSAT *************
  
 1)NOTE: PLEASE SEE EQUIPMENT GROUNDING
 NOT SHOWN FROM MAIN TO GUTTER, SUB
 PANELS. PLEASE SIZE PER 250.122.
 250.110,250.24.250.118, LOCAL
 AMENDMENTS.
 PLEASE SEE PREVIOUS PLANS CALLED FOR
 EQUIPMENT GRNDS, HOWEVER THEY WERE
 REDLINED AS BEING WRONG SIZE.
  
 2)NOTE: PLEASE SEE PLANS INDICATE "TWO"
 -SECTIONS FOR PANEL "T", PANEL SCHEDULE
 FOR PANEL "T" ALSO IS SHOWN AS 84
 CIRCUITS, HOWEVER WHAT APPEARS TO BE
 ONLY ONE PANEL SCHEDULE, WITH 42
 CIRCUITS WAS SUBMITTED?
 PLEASE CORRELATE. IF SECTION TWO TO
 PANEL "T" DOES NOT CONTAIN ANY OCP
 DEVICES OR CIRCUIT, PLEASE SHOW SEC TWO
 BLANK. IF INDEED THERE ARE CIRCUITS IN
 THIS PANEL, PLEASE SHOW.
 PLEASE ALSO SEE RISER SHOWS ONLY ONE
 PANEL SECTION FOR "T".
 215.5
  
 3)NOTE: PLEASE INDICATE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH THE
 SUBMITTED PANEL SCHEDULE.
 PLEASE SEE EM/EXT LTS, 700.12E,THE
 BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 PLEASE SEE OTHER POSSIBLE LTS SHOWN ON
 PLANS WHICH DO NOT APPEAR TO SHOW ANY
 MEANS OF CONTROL OR CIRCUITS?
 THESE HAVE BEEN REDLINED ON ONE SET OF
 PLANS.
  
 PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL THIS
 OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  