Plan Review Notes
Plan Review Notes For Permit 03101282
Permit Number 03101282
Review Stop E
Sequence Number 4
Notes
Date Text
2005-01-24 00:00:00********** NOTES REDLINED **********
  
 PLEASE SEE EQUIPMENT GROUNDING CONDUCTOR
 REDLINED ON ORIG PLANS ARE STILL SHOWN
 WRONG SIZE. PLEASE SEE 250.122 FOR MIN
 SIZE FOR 600A'S.
  
 PLEASE ALSO SEE RISER SHOWS AN EQUIPMENT
 GROUNDING CONDUCTOR FROM METER TO MAIN
 DISC. PLEASE SEE THIS IS NOT PERMITTED
 UNDER 250.6,250.24. AN EQP GRND IS ONLY
 INSTALLED "AFTER" THE FIRST MEANS OF
 DISCONNECT.
  
  
 **PLEASE SEE THESE ITEMS HAVE BEEN
 REDLINED ON PLANS AND NEED TO BE
 CORRECTED IF PLANS COME BACK IN FOR
 REVISIONS.