| Plan Review Notes For Permit 03101282 |
| Permit Number |
03101282 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-01-24 00:00:00 | ********** NOTES REDLINED ********** | | | | | | PLEASE SEE EQUIPMENT GROUNDING CONDUCTOR | | | REDLINED ON ORIG PLANS ARE STILL SHOWN | | | WRONG SIZE. PLEASE SEE 250.122 FOR MIN | | | SIZE FOR 600A'S. | | | | | | PLEASE ALSO SEE RISER SHOWS AN EQUIPMENT | | | GROUNDING CONDUCTOR FROM METER TO MAIN | | | DISC. PLEASE SEE THIS IS NOT PERMITTED | | | UNDER 250.6,250.24. AN EQP GRND IS ONLY | | | INSTALLED "AFTER" THE FIRST MEANS OF | | | DISCONNECT. | | | | | | | | | **PLEASE SEE THESE ITEMS HAVE BEEN | | | REDLINED ON PLANS AND NEED TO BE | | | CORRECTED IF PLANS COME BACK IN FOR | | | REVISIONS. |
|