Plan Review Notes
Plan Review Notes For Permit 03101282
Permit Number 03101282
Review Stop P
Sequence Number 2
Notes
Date Text
2004-01-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 BUILDING
  
 1) FROM PREVIOUS REVIEW: SHT 5 FROOR
 DRAINS/SINKS LOCATED WITHIN WALK-IN
 REFRIGERATORS OR FREEZERS IN FOOD SERV-
 ICE AND FOOD ESTABLISHMENTS SHALL BE IN-
 DIRECTLY CONNECTED TO THE SANITARY
 DRAINAGE SYSTEM BY MEANS OF AN AIR GAP.
 SECTION 802.1.2
 2) RESPONSE FROM PREVIOUS REVIEW NOTED:
 FOLLOWING INFORMATION REQUIRED.
 A) GUTTERS AND DOWNSPOUTS NOT SHOWN FOR
 EAST SIDE OF BUILDING.
 B) COMMENT RESPONSE STATES THAT IS
 ASSUMED THAT 1/2 AREA OF ROOF DRAINS TO
 THE EAST, AND 1/2 AREA OF ROOF DRAINS TO
 THE WEST. SINCE SIZING OF GUTTERS AND
 DOWNSPOUTS REQUIRE SQUARE FOOTAGE TO BE
 CALCULATED FOR EACH DOWNSPOUT, SHOW
 EXACTLY WHERE THE ROOF PITCHES FROM AND
 IN WHAT DIRECTION.
 C) SHOW HIGH AND LOW POINTS OF THE GUTT-
 ERS AND INDICATE THE SQUARE FOOTAGE BE-
 ING DRAINED BY EACH DOWNSPOUT.
 D) CLAIRFY OPTIONAL GUTTER. GUTTERS ARE
 REQUIRED.
 E) ONE PORTION OF RESPONSE INDICATES A
 3" RWL, AND ANOTHER PORTION OF RESPONSE
 INDICATES 4" RWL. PLEASE CLAIRFY.
 F) INDICATE THE HEIGHT AND WIDTH OF ALL
 GUTTERS.
 3) SEE ATTACHED SHEET CONCERNING DESIGN
 PROFESSIONALS AND FS553.80(2)(B).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]