Plan Review Notes
Plan Review Notes For Permit 03101282
Permit Number 03101282
Review Stop E
Sequence Number 2
Notes
Date Text
2003-12-30 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLANS HAD ORIGINALLY PASSED WITH
 REDLINED PLANS FOR MISSING ALL EQUIPMENT
 GROUNDING CONDUCTORS. TWO NEW SEPARATE
 SHEETS WERE TURNED IN, NOT IN SETS AND
 ONLY ONE EQUIPMENT GROUNDING CONDUCTOR
 WAS ADDED FROM GUTTER TO SUB-PANEL "S".
  
 PLEASE SEE THAT ALL OLD/VOIDED/REPLACED
 SHEETS MUST BE REMOVED FROM OLD SETS AND
 INSERT ANY AND ALL NEW SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 THESE NEW SHEETSHAVE NOT BEEN CORRECT-
 -ED TO ORIG NOTE. 250.110, 250.122, 250.
 24 ETC.
  
 PLEASE SUBMIT ANY REVISED SHEETS INTO
 SETS. REVISED SHEETS ALSO CONATIN PLUMB-
 ING DETAILS.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  