| 2004-01-05 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03101282 |
| | ADD: 1931 N DIXIE |
| | CONT: MCLAREN CONSTRUCTION |
| | TEL: (561)686-6500 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | SECOND REVIEW |
| | ACTION DENIED: |
| | |
| | 1) PROVIDE A UNITY OF TITLE FOR LOTS |
| | 11,21& 22. PLANS INDICATE WORK BEING |
| | DONE AT 1935, APPLICATION INDICATES 1931 |
| | CROSING PROPERTY LINES! TABLE 600 ISSUES |
| | |
| | 2) 1027.1.1(3) STORAGE SINGLE EXIT, |
| | SINGLE EXIT MAXIMUM TRAVEL DISTANCE TO |
| | THE EXIT DOES NOT EXCEED 50 FT. FREZZER |
| | ON THE DIAGONAL 60 FT. |
| | |
| | 3)1004.1.4 WHERE 2 OR MORE EXITS OR |
| | EXIT ACCESS DOORS ARE REQUIED, AT LEAST |
| | 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL |
| | BE PLACED A DISTANCE APART EQUAL TO NOT |
| | LESS THAN 1/2 OF THE LENGTH OF THE MAX- |
| | IMUM OVERALL DIAGONAL DIMENSION OF THE |
| | BUILDING OR AREA TO BE SERVED. |
| | EXCEPTION: SPRINKLERED BUILDINGS; 1/3RD |
| | THE LENGTH OF THE DIAGONAL OF THE BUILD- |
| | ING OR AREA TO BE SERVED. |
| | |
| | 4) 2603.5.1.2 FOAM PLASTIC INSTALLED IN |
| | A MAXIMUM OF 10" IN COOLER AND FREZZER |
| | WALLS. |
| | (4) BE PROTECTED BY AN AUTOMATIC |
| | SPRINKLER SYSTEM. WHERE THE FREZZER OR |
| | COOLER IS WITHIN A BUILDING, BOTH THE |
| | COOLER OR FREEZER AND THE PART OF THE |
| | BUILDING IN WHICH IT IS LOCATED SHALL BE |
| | FIRE SPRINKLERED. |
| | |
| | THE EXCEPTION TO THIS CODE SECTION IS |
| | 2603.5.1.3 WALK IN COOLERS: IN UNSPRINK- |
| | LERED BUILDINGS WHERE THE FOAM "DOES NOT |
| | EXCEED 4" AND THE TOTAL AGGREGATE FLOOR |
| | AREA OF THE COOLERS OR FREZEERS DOES NOT |
| | EXCEED 400 SQ. FT. |
| | THE ADDITIONAL WALK IN COOLERS AND |
| | FREEZERS ARE WELL OVER 400 SQ. FT. |
| | REQUIRING THE FIRE SPRINKLER SYSTEM. |
| | BEAUSE COLD STORAGE CONSTRUCTION FRE- |
| | QUENTLY USES INSULATION IN GREATER THICK |
| | NESSES, AN EXCEPTION IS GIVEN TO THE RE- |
| | QUIREMENT FOR THE TESTING AT THICKNESSES |
| | OF INTENDED USE. IN SUCH CASE, OTHER |
| | PROTECTION, SPECIFICICALLY AUTOMATIC |
| | FIRE SUPPRESSION IS REQUIRED INSTEAD. |
| | |
| | 5)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 6) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |