2004-01-05 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03101282
 ADD: 1931 N DIXIE
 CONT: MCLAREN CONSTRUCTION
 TEL: (561)686-6500
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 SECOND REVIEW
 ACTION DENIED:
  
 1) PROVIDE A UNITY OF TITLE FOR LOTS
 11,21& 22. PLANS INDICATE WORK BEING
 DONE AT 1935, APPLICATION INDICATES 1931
 CROSING PROPERTY LINES! TABLE 600 ISSUES
  
 2) 1027.1.1(3) STORAGE SINGLE EXIT,
 SINGLE EXIT MAXIMUM TRAVEL DISTANCE TO
 THE EXIT DOES NOT EXCEED 50 FT. FREZZER
 ON THE DIAGONAL 60 FT.
  
 3)1004.1.4 WHERE 2 OR MORE EXITS OR
 EXIT ACCESS DOORS ARE REQUIED, AT LEAST
 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL
 BE PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN 1/2 OF THE LENGTH OF THE MAX-
 IMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED.
 EXCEPTION: SPRINKLERED BUILDINGS; 1/3RD
 THE LENGTH OF THE DIAGONAL OF THE BUILD-
 ING OR AREA TO BE SERVED.
  
 4) 2603.5.1.2 FOAM PLASTIC INSTALLED IN
 A MAXIMUM OF 10" IN COOLER AND FREZZER
 WALLS.
 (4) BE PROTECTED BY AN AUTOMATIC
 SPRINKLER SYSTEM. WHERE THE FREZZER OR
 COOLER IS WITHIN A BUILDING, BOTH THE
 COOLER OR FREEZER AND THE PART OF THE
 BUILDING IN WHICH IT IS LOCATED SHALL BE
 FIRE SPRINKLERED.
  
 THE EXCEPTION TO THIS CODE SECTION IS
 2603.5.1.3 WALK IN COOLERS: IN UNSPRINK-
 LERED BUILDINGS WHERE THE FOAM "DOES NOT
 EXCEED 4" AND THE TOTAL AGGREGATE FLOOR
 AREA OF THE COOLERS OR FREZEERS DOES NOT
 EXCEED 400 SQ. FT.
 THE ADDITIONAL WALK IN COOLERS AND
 FREEZERS ARE WELL OVER 400 SQ. FT.
 REQUIRING THE FIRE SPRINKLER SYSTEM.
 BEAUSE COLD STORAGE CONSTRUCTION FRE-
 QUENTLY USES INSULATION IN GREATER THICK
 NESSES, AN EXCEPTION IS GIVEN TO THE RE-
 QUIREMENT FOR THE TESTING AT THICKNESSES
 OF INTENDED USE. IN SUCH CASE, OTHER
 PROTECTION, SPECIFICICALLY AUTOMATIC
 FIRE SUPPRESSION IS REQUIRED INSTEAD.
  
 5)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026