Plan Review Notes
Plan Review Notes For Permit 03101282
Permit Number 03101282
Review Stop P
Sequence Number 1
Notes
Date Text
2003-11-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT 5 FLOOR DRAINS LOCATED WITHIN
 WALK-IN REFRIGERATORS OR FREEZERS IN
 FOOD SERVICE AND FOOD ESTABLISHMENTS
 SHALL BE INDIRECTLY CONNECTED TO THE
 SANITARY DRAINAGE SYSTEM BY MEANS OF AN
 AIR GAP. SECTION 802.1.2
 2) SHT 5, EVERY DRY VENT CONNECTING TO A
 HORIZONTAL DRAIN SHALL CONNECT ABOVE THE
 CENTERLINE OF THE HORIZONTAL DRAIN PIPE.
 SECTION 905.3. (NO HORIZONTAL DRY VENTS)
 3) SHT 5, FLOOR DRAINS ARE NOT APPROVED
 FOR USE AS AN INDIRECT WASTE. SECTION
 802.3
 4) SHT 6, SUBMIT CALCULATIONS FOR ROOF
 DRAINS, GUTTERS AND DOWNSPOUTS PER TABLE
 1106.6. SHOW TOTAL SQUARE FOOTAGE OF
 ROOF, AND SHOW 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPETS IN CALCULATIONS
 SHOW SIZE OF GUTTERS AND DOWNSPOUTS.
 SHOW LOCATIONS OF GUTTERS AND DOWNSPOUTS
 SHOW SLOPE OF ROOF AND SLOPE OF GUTTERS.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.