| Date |
Text |
| 2003-11-04 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | |
| | 1) SHT 5 FLOOR DRAINS LOCATED WITHIN |
| | WALK-IN REFRIGERATORS OR FREEZERS IN |
| | FOOD SERVICE AND FOOD ESTABLISHMENTS |
| | SHALL BE INDIRECTLY CONNECTED TO THE |
| | SANITARY DRAINAGE SYSTEM BY MEANS OF AN |
| | AIR GAP. SECTION 802.1.2 |
| | 2) SHT 5, EVERY DRY VENT CONNECTING TO A |
| | HORIZONTAL DRAIN SHALL CONNECT ABOVE THE |
| | CENTERLINE OF THE HORIZONTAL DRAIN PIPE. |
| | SECTION 905.3. (NO HORIZONTAL DRY VENTS) |
| | 3) SHT 5, FLOOR DRAINS ARE NOT APPROVED |
| | FOR USE AS AN INDIRECT WASTE. SECTION |
| | 802.3 |
| | 4) SHT 6, SUBMIT CALCULATIONS FOR ROOF |
| | DRAINS, GUTTERS AND DOWNSPOUTS PER TABLE |
| | 1106.6. SHOW TOTAL SQUARE FOOTAGE OF |
| | ROOF, AND SHOW 1/2 AREA OF ALL VERTICAL |
| | WALLS INCLUDING PARAPETS IN CALCULATIONS |
| | SHOW SIZE OF GUTTERS AND DOWNSPOUTS. |
| | SHOW LOCATIONS OF GUTTERS AND DOWNSPOUTS |
| | SHOW SLOPE OF ROOF AND SLOPE OF GUTTERS. |
| | *********WHEN RESUBMITTING PLANS******** |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |