| Plan Review Notes For Permit 03101282 |
| Permit Number |
03101282 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-11-24 00:00:00 | DENIED: | | | 1.PLEASE PROVIDE ENERGY CALCULATIONS | | | PER 2001 FBC CHAPTER 13 SUB-CHAPTER 400. | | | | | | 2.PLEASE NOTE PLAN SHEET 6 INDICATES | | | HEIGHT OF STANDS FOR CONDENSING UNITS. | | | HEIGHT REQUIREMENTS SHALL COMPLY WITH | | | 2001 FBC 1511.7 (SEE ATTACHED). | | | | | | 3.PLEASE NOTE SHOULD ROOF WHERE THE | | | CONDENSERS ARE LOCATED BE GREATER THAN | | | 16 FT AN APPROVED PERMANENT MEANS OF | | | ACCESS WILL BE REQUIRED. | | | | | | 4.COMPLY WITH 2001 FBC 2603.5.1.2 FOR | | | CONSTRUCTION OF FREEZER/COOLERS SHOULD | | | A PREMANUFACTURED COOLER/FREEZER NOT | | | BE USED.PROVIDE MANUFACTURER SUBMITTAL | | | DATA FOR COOLER/FREEZER SHOULD A PRE- | | | MANFACTUERED UNIT NOT BE USED. | | | | | | 5.PROVIDE INFORMATION ON REFRIGERANT | | | AND LINE SETS.INDICATE MATERIAL OF | | | REFRIGERANT PIPING. | | | | | | 6.ALL REFRIGERANT PIPING INSTALLED ON | | | SITE SHALL BE TESTED IN ACCORDANCE WITH | | | 2001 FBC(M) 1108.2 AT ONE AND HALF TIMES | | | THE DESIGN PRESSURE FOR A MINIMUM OF 4 | | | HOURS. | | | | | | 7.INDICATE CONDENSATE PIPING AND | | | TERMINATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|