Plan Review Notes
Plan Review Notes For Permit 03101282
Permit Number 03101282
Review Stop M
Sequence Number 1
Notes
Date Text
2003-11-24 00:00:00DENIED:
 1.PLEASE PROVIDE ENERGY CALCULATIONS
 PER 2001 FBC CHAPTER 13 SUB-CHAPTER 400.
  
 2.PLEASE NOTE PLAN SHEET 6 INDICATES
 HEIGHT OF STANDS FOR CONDENSING UNITS.
 HEIGHT REQUIREMENTS SHALL COMPLY WITH
 2001 FBC 1511.7 (SEE ATTACHED).
  
 3.PLEASE NOTE SHOULD ROOF WHERE THE
 CONDENSERS ARE LOCATED BE GREATER THAN
 16 FT AN APPROVED PERMANENT MEANS OF
 ACCESS WILL BE REQUIRED.
  
 4.COMPLY WITH 2001 FBC 2603.5.1.2 FOR
 CONSTRUCTION OF FREEZER/COOLERS SHOULD
 A PREMANUFACTURED COOLER/FREEZER NOT
 BE USED.PROVIDE MANUFACTURER SUBMITTAL
 DATA FOR COOLER/FREEZER SHOULD A PRE-
 MANFACTUERED UNIT NOT BE USED.
  
 5.PROVIDE INFORMATION ON REFRIGERANT
 AND LINE SETS.INDICATE MATERIAL OF
 REFRIGERANT PIPING.
  
 6.ALL REFRIGERANT PIPING INSTALLED ON
 SITE SHALL BE TESTED IN ACCORDANCE WITH
 2001 FBC(M) 1108.2 AT ONE AND HALF TIMES
 THE DESIGN PRESSURE FOR A MINIMUM OF 4
 HOURS.
  
 7.INDICATE CONDENSATE PIPING AND
 TERMINATION.
  