Plan Review Notes
Plan Review Notes For Permit 03101282
Permit Number 03101282
Review Stop E
Sequence Number 1
Notes
Date Text
2003-10-28 00:00:00****** REDLINED *******
  
 1)NOTE: EQUIPMENT GROUNDING FROM MAIN TO
 GUTTER AND FROM GUTTER TO SUB-PANELS.
 250.110/ 250.122
  
 2)NOTE: 700.12E
  
 PASSED PENDING ANY COMMENTS FROM OTHER
 REVIEWERS THAT MAY HAVE AN AFFECT ON
 ELECTRICAL PLAN.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW