Plan Review Notes
Plan Review Notes For Permit 03101273
Permit Number 03101273
Review Stop B
Sequence Number 2
Notes
Date Text
2003-11-29 00:00:00*****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)PROVIDE THE RECEIPT FOR IMPACT
 FEES.
  
 2.)SEE PREVIOUS LIST, ITEM #6, ATTIC
 ACCESS REQUIRED.SHEET A2.0 SHOWS AN
 EXISTING ATTIC ACCESS SERVING THE
 EXISTING HOUSE.IF THE TRUSSES ARE TO
 REMAIN, ACCESS TO THE NEW ATTIC AREA
 (ADDITION) WILL NOT BE POSSIBLE.PLEASE
 CALL ME TO CLARIFY IF NECESSARY.
  
 3.)THE PRODUCT APPROVALS SUBMITTED,
 KINCO SINGLE HUNG IMPACT WINDOW, ARE
 ACCEPTABLE FOR SOME WINDOWS ON THE PLAN
 BUT NOT FOR THE LARGER WINDOWS.THE
 DESIGN PRESSURE FOR THE WINDOWS EXCEED
 THE MAXIMUM DESIGN LOAD CAPACITY (SEE
 THE PRODUCT APPROVAL, HIGHLIGHTED).
  
 4.)THE THERMA-TRU DOOR HAS A STATUS
 OF "PENDING" ON THE DCA WEBSITE.PER
 THE FLORIDA BUILDING COMMISSION, WE
 CANNOT ACCEPT PRODUCTS ON THE PENDING
 LIST.THIS PERMIT CAN BE ISSUED WITH A
 PROVISO THAT A SEPARATE PERMIT BE
 OBTAINED FOR THE DOOR.THERE AREN'T ANY
 EXTERIOR DOORS ON THE PLAN; IF YOU ARE
 REPLACING AN EXISTING DOOR AND WISH FOR
 IT TO BE COVERED UNDER THIS PERMIT,
 REVISE YOUR PERMIT APPLICATION,
 INDICATING WHICH DOOR IS BEING REPLACED.
  
 5.)THE PLANS SHOW WINDOWS WHICH ARE
 "EXISTING", BUT YOUR PERMIT APPLICATION
 INDICATES "WINDOW REPLACEMENT".ARE
 YOUR REPLACING ALL OF THE WINDOWS IN
 THE HOUSE?IF YOU ARE, EXISTING
 BEDROOMS WITH WINDOW BEING REPLACED
 MUST COMPLY WITH FBC1005.4, EMERGENCY
 EGRESS.THE SIZES SHOWN DO NOT COMPLY.