| Plan Review Notes For Permit 03101247 |
| Permit Number |
03101247 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-10-24 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | 1} PLEASE INDICATE WHERE THE CIRCUITS | | | FOR THE LIGHTS AND POWER ARE | | | ORIGINATING FROM. | | | | | | 2} SHOW CONDUIT SIZE AND INDICATE HOW | | | ROUTED TO THE DEVICES.ALSO NOTE | | | CONDUCTOR SIZE AND NUMBER IN EACH | | | CONDUIT. | | | | | | 3} INDICATE CIRCUIT NUMBERS AT THE | | | DEVICES. | | | | | | PLEASE SEE FIRE REVIEW COMMENTS AND | | | RESUBMIT FOR REVIEW. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|