Plan Review Notes
Plan Review Notes For Permit 03101246
Permit Number 03101246
Review Stop M
Sequence Number 3
Notes
Date Text
2004-01-07 00:00:00PROVISO:
 FAN SHUTDOWN BY DUCT SMOKE DETECTORS ARE
 REQUIRED FOR SYSTEMS THAT SHARE A COMMON
 RETURN AIR PLENUM.PLEASE PROVIDE DUCT
 SMOKE DETECTORS FOR THE SUPPLY AND
 RETURN AIR SYSTEM, PER 2001 FBC(M)
 606.2.2.
  
 FAN SHUTDOWN REQUIRED AT FINAL
 INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.