| Notes |
| Date |
Text |
| 2004-01-07 00:00:00 | PROVISO: | | | FAN SHUTDOWN BY DUCT SMOKE DETECTORS ARE | | | REQUIRED FOR SYSTEMS THAT SHARE A COMMON | | | RETURN AIR PLENUM.PLEASE PROVIDE DUCT | | | SMOKE DETECTORS FOR THE SUPPLY AND | | | RETURN AIR SYSTEM, PER 2001 FBC(M) | | | 606.2.2. | | | | | | FAN SHUTDOWN REQUIRED AT FINAL | | | INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|