| Plan Review Notes For Permit 03101246 |
| Permit Number |
03101246 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-11-05 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) SHT P2.1 SANITARY RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN. THE FLOOR | | | DRAIN IN ROOM #23 IS NOT SHOWN ON THE | | | RISER DIAGRAM. | | | 2) SHT P3.1 WATER HAMMER ARRESTORS SHALL | | | BE LOCATED NEAR THE FIXTURES IN AN | | | "EFFECTIVE RANGE" NOT IN THE CEILING. | | | PDI-WH 201 AND MANUF. INSTALL. INSTRUCT. | | | (SEE NOTE #13 PLUMBING NOTES SHT P0.1) | | | 3) A PROFESSIONAL ENGINEER SHALL SIGN | | | HIS NAME AND AFFIX HIS SEAL TO ALL PLANS | | | PER 61G15-23.002(1) & FS471.025. A CALL | | | TO THE FBPE CONFIRMED THAT A SIGNITURE | | | IS REQUIRED. | | | 4) THE SHEETS FOR PLUMBING HAVE BEEN | | | SEALED BY ONE ENGINEER AND SIGNED AND | | | DATED BY ANOTHER ENGINEER. | | | 5) ONE SET OF PLANS SHALL BE RETAINED | | | FOR OUR FILE FOR REVIEW BY THE FBPE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|