2003-11-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT P2.1 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. THE FLOOR
 DRAIN IN ROOM #23 IS NOT SHOWN ON THE
 RISER DIAGRAM.
 2) SHT P3.1 WATER HAMMER ARRESTORS SHALL
 BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING.
 PDI-WH 201 AND MANUF. INSTALL. INSTRUCT.
 (SEE NOTE #13 PLUMBING NOTES SHT P0.1)
 3) A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AND AFFIX HIS SEAL TO ALL PLANS
 PER 61G15-23.002(1) & FS471.025. A CALL
 TO THE FBPE CONFIRMED THAT A SIGNITURE
 IS REQUIRED.
 4) THE SHEETS FOR PLUMBING HAVE BEEN
 SEALED BY ONE ENGINEER AND SIGNED AND
 DATED BY ANOTHER ENGINEER.
 5) ONE SET OF PLANS SHALL BE RETAINED
 FOR OUR FILE FOR REVIEW BY THE FBPE.
  
 REVIEW BY KEN STEVENS