Plan Review Notes
Plan Review Notes For Permit 03101246
Permit Number 03101246
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-11-05 00:00:00************DENIED**********************
  
 1) PLEASE SHOW EXISTING OR NEW EMERGENCY
 LIGHTS.
  
 2) ON SHEET FA0.1 NOTE #16 FIRE ALARM
 CIRCUITS AND DEVICES SHALL BE CLASS "A"
 STYLE "C". SHOULD AND SHALL BE FIRE
 ALARM CIRCUITS AND DEVICES SHALL BE
 CLASS "A" STYLE "D".
  
 3) ALSO PLEASE SEE COMMENTS FROM OTHER
 PLAN REVIEW PROFESSIONALS.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910