| 2003-11-14 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03101246 |
| | ADD: 777 S FLAGLER SUITE# 128 |
| | PHILLIPS POINT WEST TOWER |
| | CONT: DEWHURST ASSOC |
| | TEL: (561)241-1540 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ACTION: DENIED |
| | |
| | 1) FBC 1004.1.2 EVERY ROOM OR TENANT |
| | SPACE SHALL BE PROVIDED WITH A MINIMUM |
| | OF ONE MEANS OF EGRESS. EVERY ROOM OR |
| | TENANT SPACE WHICH HAS AN OCCUPANT LOAD |
| | OF 50 OR PERSONS OR IN WHICH THE TRAVEL |
| | DISTANCE FROM THE MOST REMOTE POINT TO |
| | THE EXIT ACCESS FROM THE ROOM OR TENANT |
| | SPACE EXCEEDS 75 FT SHALL HAVE NOT LESS |
| | THAN TWO EGRESS DOORS. |
| | |
| | 2) THE COMMON PATH OF TRAVEL SHALL NOT |
| | EXCEED 75 FT. EXCEPTION: AS MODIFIED BY |
| | SECTION 1018. 1020.1(4) MAXIMUM TRAVEL |
| | DISTANCE SINGLE EXIT 75 FT. |
| | |
| | 3)1004.1.4 WHERE 2 OR MORE EXITS OR |
| | EXIT ACCESS DOORS ARE REQUIED, AT LEAST |
| | 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL |
| | BE PLACED A DISTANCE APART EQUAL TO NOT |
| | LESS THAN 1/2 OF THE LENGTH OF THE MAX- |
| | IMUM OVERALL DIAGONAL DIMENSION OF THE |
| | BUILDING OR AREA TO BE SERVED. |
| | EXCEPTION (2) 1/3RD DISTANCE FOR FULLY |
| | SPRINKLERED BUILDINGS. |
| | |
| | 4) OFFICE# 13 ENTRY DOOR MUST MEET: |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | 5)1204.2 SURROUNDING MATERIALS; |
| | THE WALLS & FLOORS OF ALL PUBLIC REST- |
| | ROOMS SHALL BE LINED WITH NONABSORBANT |
| | MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE |
| | FLOOR. |
| | |
| | 6) 609.2.1 TYPE I & II CONSTRUCTION: |
| | WOOD BACKING TO BE FIRE RESISTANT TREAT- |
| | ED WOOD. |
| | |
| | 7)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |