2003-10-25 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 2) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 3) AN APPROVED MAIN OUTLET, WHEN PROVID-
 ED, SHALL BE LOCATED ON A WALL OR FLOOR
 AT OR NEAR THE DEEPEST POINT IN THE POOL
 FOR EMPTYING OR CIRCULATION, OR BOTH OF
 THE WATER IN THE POOL. (NO DRAIN SHOWN
 IN THE POOL)SEC 424.2.21.3
 4) SECTION 424.2.21.4 HYDROSTATIC RELIEF
 DEVISE. IN AREAS OF ANTICIPATED WATER
 TABLE AN APPROVED HYDROSTATIC RELIEF DE-
 VISE SHALL BE INSTALLED.
  