| 2003-12-06 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 FUEL GAS |
| | |
| | A) THE FOLLOWING INFORMATION STILL RE- |
| | QUIRED FOR GAS PERMIT. |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. SEE PLANS OF SECTIONS OF |
| | PIPE WITH NO MEASURMENTS. |
| | 2. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). NOT SHOWN |
| | 3. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. RESPONSE NOTED, |
| | BUT SECTION 303.3 STATES, "FUEL-FIRED |
| | APPLIANCES SHALL NOT BE LOCATED IN, OR |
| | OBTAIN COMBUSTION AIR FROM, ANY OF THE |
| | FOLLOWING ROOMS OR SPACES: |
| | 1. SLEEPING ROOMS. 2. BATHROOMS. 3. TOI- |
| | LET ROOMS. 4. STORAGE CLOSETS ECT. |
| | 4) IF THE PRESSURE FOR THIS SYSTEM IS |
| | 2 LBS, THEN REGULATORS SHALL BE REQUIRED |
| | AT EACH APPLIANCE. 1" PIPE WILL SUPPLY |
| | UP TO 260,000 BTU'S UP TO 60' WITH .5PSI |
| | SO 2 LB IS NOT NEEDED. PLEASE CLAIRFY. |
| | |