| Date |
Text |
| 2003-10-25 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | |
| | 1) SANITARY RISER DIAGRAM DOES NOT MEET |
| | CODE REQUIREMENTS. KITCHEN AND BAR SINK |
| | ARE NOT VENTED. SUBMIT SANT. RISER DIA- |
| | GRAM IN AN ISOMETRIC FORM. SHOW VENTS. |
| | WASH MACHINE REQUIRES A C/O AT 4' ABOVE |
| | THE FLOOR. 708.10 - 901.2.1 |
| | 2) SEPARATE PERMIT REQUIRED FOR GAS. |
| | THE FOLLOWING INFORMATION IS REQUIRED AT |
| | APPLICATION FOR GAS PERMIT. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | F. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. FOR WATER HEATER |
| | AND DRYER. |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | 3) SEE ATTACHED SHEET CONCERNING DESIGN |
| | PROFESSIONALS. TITLE BLOCK REQUIRED WITH |
| | INFORMATION STATED PER 61G1-16.004 |
| | |