| Plan Review Notes For Permit 03101044 |
| Permit Number |
03101044 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-08 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLA. ADMINISTRATIVE CODE | | | FLA. STATUTES | | | | | | 1) SHT P1.1 SANITARY RISER UP TO THE | | | THIRD FLOOR, AND RISER WITH LAUNDRY ROOM | | | ON FIRST FLOOR DO NOT MEET CODE REQUIRE- | | | MENTS. 908.3 CONNECTION AT DIFFERENT | | | LEVELS, THE UPPER FIXTURE SHALL NOT BE A | | | WATER CLOSET. (SEE EXAMPLE OF RISERS TO | | | MEET CODE REQUIREMENTS). | | | 2) 61G1-16.003 THE PERSONAL SEAL, SIGNA- | | | TURE AND DATE SHALL APPEAR ON EACH SHEET | | | - THE DATE IS NOT AFFIXED ON SEAL. FS | | | 481.2005 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|