Plan Review Notes
Plan Review Notes For Permit 03101044
Permit Number 03101044
Review Stop B
Sequence Number 1
Notes
Date Text
2004-01-08 00:00:001. EXPOSURE RATING- CODES AND STANDARD
 #1 WINDLOADS AS PER SECTION 1606 FBC
 "B"PAGE A1.1 EXPOSURE LISTED AS "C".
 CORRECT THE EXPOSURE RATING.
  
 2. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 3.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4.NOT ALL PRODUCT APPROVALS ON FBC
 PRODUCT APPROVAL SITE.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.PRODUCT APPROVALS MISSING FOR
 ARCHED HEADER DOORS.
  
 6.SPECIFY IN MORE DETAIL SHOWING
 EXISITING AND NEW WINDOWS AND DOORS.
  
 7.WINDOWS NOT APPROVED TO MEET DESIGN
 PRESSURES.SEE ATTACHED ASCE-98 SPEC'S.
  
 8.COMPLETE ATTACHED SCHEDULE OF
 OPENING PROTECTIVE DEVICES.
  
 9.FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 10.S6.0/F2 FBC 2304.3.4 WHEN WOOD
 JOISTS ARE CLOSER THAN 18" TO GROUND
 THEY SHALL BE OF A ROT RESISTAND TREATED
 WOOD.
  
 11.SHOW WINDOW BUCK DETAIL.
 1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 12.1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
 1707.4.5.2 MULLIONS SHALL BE
 DESIGN-ED TO TRANSFER THE DESIGN
 PRESSURE LOADSAPPLIED BY THE WINDOW OR
 DOOR ASSEMBLIESTO THE ROUGH OPENING
 SUBTRATE.
  
 13.ATTIC VENTILATION SHALL COMPLY TO
 FBC 2309.7.1SHOW DETAILS.
  
 14.ATTICS WITH OUT STORAGE SHALL HAVE
 A 10LBS LIVE LOAD FBC TABLE 1604.1
  
 15.PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 16.FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR
 SUPPORTSAT SPACING NOT TO EXCEED 3 FT
 OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 17.SUBMIT AN ENGINEERS REPORT FOR
 EXISTING FOOTINGS SUPPORTING NEW LOADS.
  
 18.SUBMIT DETAIL FOR GUARD RAILS
 1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
 1608.2.3 THE GUARDRAIL SYSTEM SHALL
 BE DESIGNED AND CONSTRUCTED TO RESIST A
 200 LB CONCENTRATED HORIZONTAL LOAD
 APPLIED ON A 1 SQ FT AREA AT ANY POINT
 IN THE SYSTEM INCLUDING INTERMEDIATE
 RAILS OR OTHER ELEMENTS SERVING THIS
 PURPOSE.
  
 19.FIRE SPRINKLER SYSTEM A1.1
 SUBMIT DETAILS FOR FIRE SPRIKLER SYSTEM
 SYSTEM TO BE TYPE 13.
  
 20.SWIMMING POOL BARRIERS SHALL COMPLY
 WITH FBC SEC. 424.2.17
  
 21.905.2.2 WHERE THE DWELLING OR
 DWELLING UNIT CONTAINS MORE THAN ONE
 STORY, DETECTORS ARE REQUIRED ON EACH
 STORY, LOCATED IN CLOSE PROXIMITY TO THE
 STAIRWAY LEADING TO THE FLOOR ABOVE.
  
 22. R-3 EGRESS DOOR/ 32" CLEAR:
 1003.2.1. THE WIDTH OF THE MEANS OF
 EGRESS SHALL BE DETERMINED FROM THE
 OCCUPANTS SERVED IN ACCORDANCE WITH
 TABLE 1004.R-3 MINIMUM CLEAR OPENING OF
 EXIT DOOR IS 32". 1012.1.1 EGRESS DOORS
 USED IN THE EXIT ACCESS SHALL PROVIDE A
 CLEAR OPENING OF NOT LESS THAN 32" WIDE.
 1012.1.7 REQUIRED EXIT DOORS SHALL BE
 OPENABLE FROM THE INSIDE WITHOUT THE USE
 OF A KEY OR TOOL, OR SPECIAL KNOWEDGE OR
 EFFORT. MANUALLY OPERATED FLUSH BOLTS OR
 SURFACE BOLTS ARE PROHIBITED. ALL HARD-
 WARE MUST BE DIRECT ACTING REQUIRING NO
 MORE THAN ONE OPERATION.
  
 23.FBC 1005.4.5 (GLITCH AMENDMENTS
 JULY 1, 2003) REQUIRES AT LEAST ONE
 MEANS OF ESCAPE FROM A DWELLING WHEN
 SHUTTERED FOR IMPACT PROTECTION. THE
 MEANS OF ESCAPE SHALL BE WITHIN THE
 FIRST FLOOR OF THE DWELLING AND CAN NOT
 BE LOCATED IN A GARAGE. OCCUPANTS IN ANY
 PART OF THE DWELLING SHALL HAVE ACCESS
 TO IT WITHOUT HAVING TO PASS THROUGH A
 LOCKABLE DOOR NOT UNDER THEIR CONTROL.
 INDICATE HOW COMPLIANCE WILL BE
 ACHIEVED.
  
 24. 1803.1.3 EXCAVATION FOR ANY PURPO
 SHALL NOT EXTEND WITHIN 1 FT OF THE
 ANGLE OF REPOSE OR NARURAL SLOPE OF THE
 SOIL UNDER ANY FOOTING OR FOUNDATION,
 UNLESS SUCH FOOTING OR FOUNDATION IS
 FIRST PROPERLY UNDERPINNED OR PROTECTED
 AGAINST SETTLEMENT.VERIFY DISTANCES
 TO NEW POOL EXCAVATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 561-805-6672