| 2003-10-30 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03101043 |
| | ADD: 3611 S DIXIE HWY |
| | CONT: ANNUNZIATA BUILDING |
| | TEL: (561)753-4719 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ACTION: DENIED |
| | |
| | 1) 1006.2.2 EXTERIOR STAIRWAYS SHALL BE |
| | PERMITTED WHERE AT LEAST ONE DOOR FROM E |
| | ACH TENANT OPENS ONTO A ROOFED-OVER OPEN |
| | BALCONY, PORCH OR GALLERY, OR SIMILAR |
| | SPACE. |
| | |
| | 2)1015.2 HEIGHT. GUARDRAILS SHALL |
| | FORM A VERTICAL PROTECTIVE BARRIER NOT |
| | LESS THAN 42" HIGH. |
| | 1015.3 OPENINGS. OPEN GUARDRAILS |
| | SHALL HAVE INTERMEDIATE RAILS OR ORNA- |
| | MENTAL PATTERNS SUCH AS A 4" DIAMETER |
| | SPHERE CAN NOT PASS THROUGH. A BOTTOM |
| | RAIL OR CURB SHALL BE PROVIDED THAT WILL |
| | REJECT THE PASSAGE OF 2" DIAMETER |
| | SPHERE. |
| | |
| | 3) PROVIDE ADD INFO: WHAT TYPE OF OCCUPA |
| | NY IS ON THE 2ND FLOOR? OCC. LOAD?TABLE |
| | 1004 MINIMUM STAIR WITH 44" FOR OCC LOAD |
| | LESS THAN 50 A 36" STAIR IS OK! |
| | |
| | 4) 1007.3.1 TREADS & RISERS, RISERS |
| | SHALL BE A MAXIMUM OF 7" IN HEIGTH. |
| | |
| | 5)1606.1.4(1) IN WIND BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| | ASSUMED TO BE OPENINGS UNLESS SUCH |
| | GLAZING IS IMPACT RESISTANT OR PROTECTED |
| | WITH AN IMPACT RESISTANT COVERING MEET- |
| | ING THE REQUIREMENTS OF SSTD 12, ASTM |
| | E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| | GLAZED OPENINGS LOCATED WITHIN 30 FT |
| | OF GRADE SHALL MEET THE REQUIREMENTS OF |
| | LARGE MISSLE TEST. |
| | FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORT, SBCCI OR DADE COUNTY |
| | REPORT ARE ACCEPTED. MISSING THE |
| | PRODUCT APPROVAL FOR NEW DOOR. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |