| 2003-11-17 00:00:00 | UNSAT |
| | |
| | 1) THE LETTER FROM THE ARCHITECT |
| | ADDRESSING THE TRUSSES DOES NOT HAVE AN |
| | ORIGINAL WET SIGNATURE. THERE IS NOTHING |
| | ON THE PLANS INDICATING THE MODEL TO |
| | WHICH THE LETTER REFERS. |
| | |
| | 2) SPECIFY ON THE PLANS THAT THE WWF IN |
| | THE SLAB WILL BE SUPPORTED AT 3'OC AS |
| | REQUIRED BY FBC 1909.3. |
| | |
| | 3) THE STAIRS FROM THE LOFT TO THE BED |
| | ROOMS DO NOT COMPLY WITH FBC 1007.3. THE |
| | SUM OF TWO RISERS AND A TREAD EXCLUSIVE |
| | OF THE NOSING SHALL BE NO LESS THAN 24" |
| | NOR MORE THAN 25". |
| | |
| | 4) HANDRAILS 34"- 38" HIGH ARE REQUIRED |
| | FOR STAIRWAYS WITH FOUR OR MORE RISERS |
| | PER FBC 1007.5. HANDRAILS MUST PROVIDE |
| | GRASPABILITY AS REQUIRED BY FBC 1007.5.3 |
| | GUARDRAILS FOR DWELLING SHALL BE A MIN. |
| | OF 36" HIGH PER FBC 1026.5. |
| | |
| | 5) THE 120 SQ.IN. VENT IN THE GARAGE CAN |
| | NOT BE LOCATED IN THE WALL ON THE ZERO |
| | LOT LINE. NO OPENINGS ARE ALLOWED IN |
| | THIS WALL PER FBC TABLE 600. |
| | |
| | 6) ON THE FRAMING PLAN ON A7 A LINTEL |
| | (L1) IS INDICATED AT THE SHOWER IN THE |
| | MASTER BEDROOM. NO OPENING IS SHOWN ON |
| | THE FLOOR PLAN AT THIS LOCATION. PLEASE |
| | CLARIFY. |
| | |
| | 7) PRODUCT APPROVALS SUBMITTED WITH |
| | APPLICATIONS AFTER OCTOBER 1, 2003 ARE |
| | REQUIRED TO COMPLY WITH THE STATE OF |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION SEE THE STATE WEBSITE AT WWW |
| | FLORIDABUILDING.ORG. PRODUCTS WITH STATE |
| | APPROVAL ARE REQUIRED TO BE SUBMITTED |
| | WITH A COVER SHEET WHICH LISTS THE |
| | PRODUCT IDENTITY NUMBER FROM THE STATE. |
| | IF THE PRODUCT DOES NOT HAVE A STATEWIDE |
| | PRODUCT APPROVAL, SUBMIT AN APPLICATION |
| | FOR LOCAL PRODUCT APPROVAL PER RULE |
| | 9B-72. SEE ATTACHMENT. |
| | |
| | 8) FBC 1606.1.4 REQUIRES EXTERIOR |
| | GLAZING PROTECTION IN WINDBORNE DEBRIS |
| | REGIONS. PROVIDE (2) PRODUCT APPROVALS, |
| | KEY PLANS AND INSTALLATION SCHEDULES |
| | INDICATING THE SPECIFIC TYPES OF ANCHORS |
| | TO BE USED FOR STORM PANELS. |
| | |
| | 9)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR THE SINGLE OUTSWING FRONT |
| | DOOR. THE ONE THAT WAS SUBMITTED IS FOR |
| | DOUBLE OUTSWING DOORS ONLY. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |