| 2003-12-31 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03100871 |
| | ADD: 2275 PALM BEACH LAKES BLVD |
| | CONT: HALLMARK BUILDERS |
| | TEL: (561)512-5512 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | SECOND REVIEW: DENIED |
| | |
| | 1) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | 1) NEW OVERHEAD DOORS |
| | |
| | 2) 1707.4.3 EACH EXTERIOR DOOR |
| | ASSEMBLY NOT COVERED BY 1707.4.2 |
| | (GLAZED DOORS) SHALL BE LISTED AND TEST- |
| | ED FOR A PERIOD EQUAL TO THE QUANITY |
| | 3600/ V WHERE THE TIME PERIOD IS IN |
| | SECTIONS AND V IS IN MILES PER HR TAKEN |
| | FROM FIGURE 1606. THE TIME PERIOD SHALL |
| | ALSO INCLUDE A 10 SECOND PERIOD AT A |
| | LOAD EQUAL TO 1.5 TIMES THE DESIGN |
| | PRESSURE. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | ARE ACCEPTED. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |